7
Data register
Name
Unit
Kind of data
Range
R/W
DT30020
Voltage harmonics
alarm(OFF threshold)
OUT2
0.01%
Unsigned 16bit 0 to 40000
R/W
DT30021
Voltage harmonics
alarm(phase) OUT2
-
Unsigned 16bit
0:All,1:Phase1(line1-2),
2:Phase2(line2-3),
3:Phase3(line3-1)
R/W
DT30022
Current THD alarm
(ON threshold) OUT1
0.01%
Unsigned 16bit 0 to 40000
R/W
DT30023
Current THD alarm
(OFF threshold) OUT1
0.01%
Unsigned 16bit 0 to 40000
R/W
DT30024
Current THD alarm
(phase) OUT1
-
Unsigned 16bit 0:All,1:Phase1, 2:Phase2,
3:Phase3
R/W
DT30025
Current THD alarm
(ON threshold) OUT2
0.01%
Unsigned 16bit 0 to 40000
R/W
DT30026
Current THD alarm
(OFF threshold) OUT2
0.01%
Unsigned 16bit 0 to 40000
R/W
DT30027
Current THD alarm
(phase) OUT2
-
Unsigned 16bit 0:All,1:Phase1, 2:Phase2,
3:Phase3
R/W
DT30028
Voltage THD alarm
(ON threshold) OUT1
0.01%
Unsigned 16bit 0 to 40000
R/W
DT30029
Voltage THD alarm
(OFF threshold) OUT1
0.01%
Unsigned 16bit 0 to 40000
R/W
DT30030
Voltage THD alarm
(phase) OUT1
-
Unsigned 16bit
0:All,1:Phase1(line1-2),
2:Phase2(line2-3),
3:Phase3(line3-1)
R/W
DT30031
Voltage THD alarm
(ON threshold) OUT2
0.01%
Unsigned 16bit 0 to 40000
R/W
DT30032
Voltage THD alarm
(OFF threshold) OUT2
0.01%
Unsigned 16bit 0 to 40000
R/W
DT30033
Voltage THD alarm
(phase) OUT2
-
Unsigned 16bit
0:All,1:Phase1(line1-2),
2:Phase2(line2-3),
3:Phase3(line3-1)
R/W
DT30034
Current unbalancing
alarm(ON threshold)
OUT1
0.01%
Unsigned 32bit 0 to 99999
R/W
DT30035
DT30036
Current unbalancing
alarm(OFF threshold)
OUT1
0.01%
Unsigned 32bit 0 to 99999
R/W
DT30037
DT30038
Current unbalancing
alarm(ON threshold)
OUT2
0.01%
Unsigned 32bit 0 to 99999
R/W
DT30039
DT30040
Current unbalancing
alarm(OFF threshold)
OUT 2
0.01%
Unsigned 32bit 0 to 99999
R/W
DT30041
DT30042
Voltage unbalancing
alarm(ON threshold)
OUT1
0.01%
Unsigned 32bit 0 to 99999
R/W
DT30043
DT30044
Voltage unbalancing
alarm(OFF threshold)
OUT1
0.01%
Unsigned 32bit 0 to 99999
R/W
DT30045
DT30046
Voltage unbalancing
alarm(ON threshold)
OUT2
0.01%
Unsigned 32bit 0 to 99999
R/W
DT30047
DT30048
Voltage unbalancing
alarm(OFF threshold)
OUT2
0.01%
Unsigned 32bit 0 to 99999
R/W
DT30049
DT30050
Under current alarm
(phase) OUT1
-
Unsigned 16bit 0:All,1:Phase1, 2:Phase2,
3:Phase3
R/W
DT30051
Under current alarm
(phase) OUT2
-
Unsigned 16bit 0:All,1:Phase1, 2:Phase2,
3:Phase3
R/W
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]