129
Data identification
Name
Data
format
unit
byte
range
R/W
DI
3
DI
2
DI
1
DI
0
04 05 02
26 PF alarm(phase) OUT1
X
-
1
0:All,1:Phase1,
2:Phase2,3:Phase3
R/W
27 PF alarm
(ON threshold)OUT2
X.XXX
-
2
0 to 1000
R/W
28 PF alarm
(OFF threshold)OUT2
X.XXX
-
2
0 to 1000
R/W
29 PF alarm(phase) OUT2
X
-
1
0:All,1:Phase1,
2:Phase2,3:Phase3
R/W
2A
Current harmonics
alarm(ON threshold)
OUT1
XXX.XX
0.01%
3
0 to 40000
R/W
2B
Current harmonics
alarm(OFF threshold)
OUT1
XXX.XX
0.01%
3
0 to 40000
R/W
2C Current harmonics
alarm(phase) OUT1
X
-
1
0:All,1:Phase1,
2:Phase2,3:Phase3
R/W
2D
Current harmonics
alarm(ON threshold)
OUT2
XXX.XX
0.01%
3
0 to 40000
R/W
2E
Current harmonics
alarm(OFF threshold)
OUT2
XXX.XX
0.01%
3
0 to 40000
R/W
2F Current harmonics
alarm(phase)OUT2
X
-
1
0:All,1:Phase1,
2:Phase2,3:Phase3
R/W
30
Voltage harmonics
alarm(ON threshold)
OUT1
XXX.XX
0.01%
3
0 to 40000
R/W
31
Voltage harmonics
alarm(OFF threshold)
OUT1
XXX.XX
0.01%
3
0 to 40000
R/W
32 Voltage harmonics
alarm(phase)OUT1
X
-
1
0:All,1:Phase1(line1-2),
2:Phase2(line2-3),
3:Phase3(line3-1)
R/W
33
Voltage harmonics
alarm(ON threshold)
OUT2
XXX.XX
0.01%
3
0 to 40000
R/W
34
Voltage harmonics
alarm(OFF threshold)
OUT2
XXX.XX
0.01%
3
0 to 40000
R/W
35 Voltage harmonics
alarm(phase)OUT2
X
-
1
0:All,1:Phase1(line1-2),
2:Phase2(line2-3),
3:Phase3(line3-1)
R/W
36 Current THD alarm
(ON threshold) OUT1
XXX.XX
0.01%
3
0 to 40000
R/W
37 Current THD alarm
(OFF threshold) OUT1
XXX.XX
0.01%
3
0 to 40000
R/W
38 Current THD alarm
(phase) OUT1
X
-
1
0:All,1:Phase1,
2:Phase2,3:Phase3
R/W
39 Current THD alarm
(ON threshold) OUT2
XXX.XX
0.01%
3
0 to 40000
R/W
3A Current THD alarm
(OFF threshold) OUT2
XXX.XX
0.01%
3
0 to 40000
R/W
3B Current THD alarm
(phase) OUT2
X
-
1
0:All,1:Phase1,
2:Phase2,3:Phase3
R/W
3C Voltage THD alarm
(ON threshold) OUT1
XXX.XX
0.01%
3
0 to 40000
R/W
3D Voltage THD alarm
(OFF threshold) OUT1
XXX.XX
0.01%
3
0 to 40000
R/W
3E Voltage THD alarm
(phase) OUT1
X
-
1
0:All,1:Phase1(line1-2),
2:Phase2(line2-3),
3:Phase3(line3-1)
R/W
3F Voltage THD alarm
(ON threshold) OUT2
XXX.XX
0.01%
3
0 to 40000
R/W
40 Voltage THD alarm
(OFF threshold) OUT2
XXX.XX
0.01%
3
0 to 40000
R/W