124
Change transmission speed
It changes the transmission speed after it returns the response.
・
Command from master; Control code 17H
68H A0 A1 A2 A3 A4 A5 68H
17H
01H
Z
CS 16H
Transmission address
Control code
Transmission speed
(bit flag)
Transmission speed
(bit flag)
bit
Transmission speed [bps]
Bit 7
38400
Bit 6
19200
Bit 5
9600
Bit 4
4800
Bit 3
2400
Bit 2
1200
Bit 1
vacant
Bit 0
vacant
・
Response from slave (normal)
68H A0 A1 A2 A3 A4 A5 68H
97H
01H
Z
CS 16H
Transmission address
Transmission speed
(bit flag)
Change password
It changes password.
It is available only with pressing <MODE> key (programming key).
Without pressing programming key, it doesn’t response.
For changing password, authorization level (PA0) should be designated, but only ‘0’ is supported.
・
Command from master; Control code 18H
68H
A0
A1
A2
A3
A4
A5
68H
18H
0CH
⇒
continue
Transmission address
Control code
⇒
Continue
DI0 DI1 DI2 DI3
PA
P0
P1
P2
⇒
continue
34 3F 33 37
(Add 33H to 01 0C 00 04)
(Only ”0” is supported.)
Designate authorization
level (33H fix)
Designate the present
password (P2: 33H fix)
⇒
continue
PAn
P0n
P1n
P2n
CS 16H
Authorization level for password
to change (33H fix)
New password
(P2n: 33H fix)
・
Response from slave (normal)
68H A0 A1 A2 A3 A4 A5 68H 18H
04H
⇒
continue
Transmission address
PAn
P0n
P1n
P2n
CS
16H
Authorization level for changed
password (33H fix)
Changed password
(P2n: 33H fix)