131
Data identification
Name
Data
format
unit
byte
range
R/W
DI
3
DI
2
DI
1
DI
0
04 05 02
5B Over frequency alarm
(ON threshold) OUT2
XXX.XX
0.01Hz
3
0.01 to 100.00
R/W
5C Over frequency alarm
(OFF threshold) OUT2
XXX.XX
0.01Hz
3
0.01 to 100.00
R/W
5D Over frequency alarm
(phase)OUT2
X
-
1
0:All,1:Phase1,
2:Phase2,3:Phase3
R/W
5E Under frequency alarm
(ON threshold) OUT1
XXX.XX
0.01Hz
3
0.01 to 100.00
R/W
5F Under frequency alarm
(OFF threshold) OUT1
XXX.XX
0.01Hz
3
0.01 to 100.00
R/W
60 Under frequency alarm
(phase)OUT1
X
-
1
0:All,1:Phase1,
2:Phase2,3:Phase3
R/W
61 Under frequency alarm
(ON threshold) OUT2
XXX.XX
0.01Hz
3
0.01 to 100.00
R/W
62 Under frequency alarm
(OFF threshold) OUT2
XXX.XX
0.01Hz
3
0.01 to 100.00
R/W
63 Under frequency alarm
(phase)OUT2
X
-
1
0:All,1:Phase1,
2:Phase2,3:Phase3
R/W
64 Power demand alarm
(Power type) OUT1
X
-
1
0: active power,
1: reactive power,
2: apparent power,
3: active power(export),
4: reactive power(export)
R/W
65 Power demand alarm
(ON threshold) OUT1
XXXXX.XXX
0.001
4
0 to 99999.999
R/W
66 Power demand alarm
(OFF threshold) OUT1
XXXXX.XXX
0.001
4
0 to 99999.999
R/W
67 Power demand alarm
(target) OUT1
XXXXX.XXX
0.001
4
0 to 99999.999
R/W
68 Power demand alarm
(hysteresis) OUT1
XXX
1%
2
0 to 100%
R/W
69 Power demand alarm
start-time OUT1
XX
1min,
1
1 to 30
R/W
6A Power demand alarm
(Power type) OUT2
X
-
1
0: active power,
1: reactive power,
2: apparent power,
3: active power(export),
4: reactive power(export)
R/W
6B Power demand alarm
(ON threshold) OUT2
XXXXX.XXX
0.001
4
0 to 99999.999
R/W
6C Power demand alarm
(OFF threshold) OUT2
XXXXX.XXX
0.001
4
0 to 99999.999
R/W
6D Power demand alarm
(target) OUT2
XXXXX.XXX
0.001
4
0 to 99999.999
R/W
6E Power demand alarm
(hysteresis) OUT2
XXX
1%
2
0 to 100%
R/W
6F Power demand alarm
start-time OUT2
XX
1min,
1
1 to 30
R/W
70 Current demand alarm
(ON threshold)OUT1
XXX.X
0.1%
2
0 to 1200
R/W
71 Current demand alarm
(OFF threshold)OUT1
XXX.X
0.1%
2
0 to 1200
R/W
72 Current demand alarm
(phase)OUT1
X
-
1
0:All,1:Phase1,
2:Phase2,3:Phase3
R/W
73 Current demand alarm
(ON threshold)OUT2
XXX.X
0.1%
2
0 to 1200
R/W
74 Current demand alarm
(OFF threshold)OUT2
XXX.X
0.1%
2
0 to 1200
R/W
75 Current demand alarm
(phase)OUT2
X
-
1
0:All,1:Phase1,
2:Phase2,3:Phase3
R/W