9
Data register
Name
Unit
Kind of data
Range
R/W
DT30093
Power demand alarm
(power type) OUT2
-
Unsigned 16bit
0: active power,
1: reactive power,
2: apparent power,
3: active power(export),
4: reactive power(export)
R/W
DT30094
Power demand alarm
(ON threshold) OUT2
0.001 kW
/kvar/kVA
Unsigned 32bit 0 to 99999999
R/W
DT30095
DT30096
Power demand alarm
(OFF threshold) OUT2
0.001 kW
/kvar/kVA
Unsigned 32bit 0 to 99999999
R/W
DT30097
DT30098
Power demand alarm
(target) OUT2
0.001 kW
/kvar/kVA
Unsigned 32bit 0 to 99999999
R/W
DT30099
DT30100
Power demand alarm
(hysteresis) OUT2
1%
Unsigned 16bit 0 to 100%
R/W
DT30101
Power demand alarm
start-time OUT2
1min,
Unsigned 16bit 1 to 30
R/W
DT30102
Current demand alarm
(ON threshold) OUT1
0.1%
Unsigned 16bit 0 to 1200
R/W
DT30103
Current demand alarm
(OFF threshold)OUT1
0.1%
Unsigned 16bit 0 to 1200
R/W
DT30104
Current demand alarm
(phase)OUT1
-
Unsigned 16bit 0:All,
1:Phase1, 2:Phase2, 3:Phase3
R/W
DT30105
Current demand alarm
(ON threshold) OUT2
0.1%
Unsigned 16bit 0 to 1200
R/W
DT30106
Current demand alarm
(OFF threshold)OUT2
0.1%
Unsigned 16bit 0 to 1200
R/W
DT30107
Current demand alarm
(phase)OUT2
-
Unsigned 16bit 0:All,
1:Phase1, 2:Phase2, 3:Phase3
R/W
DT30108
Power demand type
-
Unsigned 16bit 0:peak demand,
1:sliding block,
2:fixed block,
3:30-min demand
R/W
DT30109
Power demand interval1
1min,
Unsigned 16bit 1 to 60
R/W
DT30110
Power demand interval2
1min,
Unsigned 16bit 1 to 60
R/W
DT30111
Current demand interval
1min,
Unsigned 16bit 1 to 60
R/W
DT30112
30-min demand
calcuration method
-
Unsigned 16bit 0:addition, 1:average
R/W
DT30113
Power input type
-
Unsigned 16bit 0:CT inpuit 1:pulse input
R/W
DT30114
Pulse type
-
Unsigned 16bit 0:kWh, 1:Pulse
R/W
DT30115
Pulse rate (electric
power conversion)
0.001kWh Unsigned 32bit 1 to 100000
R/W
DT30116
DT30117
Pulse constant value
pulse/kWh Unsigned 16bit 0:50000, 1:2000
R/W
DT30118
Under current
(ON threshold)
0.1%
Unsigned 16bit 0 to 1000
R/W
DT30119
Under current
(OFF threshold)
0.1%
Unsigned 16bit 0 to 1000
R/W
DT30300
Reset all integral value
-
Unsigned 16bit 0:No
1:Yes
R/W
DT30301
Reset integral value 1
-
Unsigned 16bit 0:No
1:Yes
R/W
DT30302
Reset integral value 2
-
Unsigned 16bit 0:No
1:Yes
R/W
DT30303
Reset integral value 3
-
Unsigned 16bit 0:No
1:Yes
R/W
DT30304
Reset count value 1
-
Unsigned 16bit 0:No
1:Yes
R/W
DT30305
Reset count value 2
-
Unsigned 16bit 0:No
1:Yes
R/W
DT30306
Reset log data
-
Unsigned 16bit 0:No
1:Yes
R/W
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]