Report system of central display for alarm by each line
Routing setting of above system by setting tool
When line A has 2 inputs, line B has 3 inputs (ERR21 and ERR31 are common. ERR22 and ERR32
are common.) , line C has 3 inputs (ERR41,ERR51 and ERR61 are common. ERR42, ERR52 and
ERR62 are common. ERR43, ERR53 and ERR63 are common.), connect as below.
“-“ shows that it is not connected.
2 or more inputs are allocated to same terminal number, when at least 1 signal input, output to
master. Slave’s number to be connected to same terminal number is max. 99.
Terminal
Master
00
Terminal
Slave
01
Slave
02
Slave
03
Slave
04
Slave
05
Slave
06
0
LMP1
0
ERR11
- - -
1 LMP2
1
ERR12
- - -
2
LMP3
2
- ERR21
ERR31 -
3 LMP4
3
- ERR22
ERR32 -
4
LMP5
4
- ERR23
ERR33 -
5 LMP6
5
- - -
ERR41
ERR51
ERR61
6
LMP7
6
- - -
ERR42
ERR52
ERR62
Output
7 LMP8
Input
7
- - -
ERR43
ERR53
ERR63
Notes
:・
In order to transfer input to the other unit, signal should be input over polling time.
・
When signal is input to slave, it reflects to master at polling timing.
It delays for polling time.
Line A
Alarm Display
LMP1
LMP2
LMP3
LMP4
LMP5
LMP6
LMP7
LMP8
Master 00
From equipment
Alarm output ERR11
larm output ERR12
Slave 02
Line B
A
From
equipment
Alarm output
Alarm output
Alarm output
ERR21
ERR22
ERR23
Intput terminal
From
equipment
Alarm output
Alarm output
Alarm output
ERR31
ERR32
ERR33
Intput terminal
Slave 03
Slave 06
From
equipment
Alarm output
Alarm output
Alarm output
ERR61
ERR62
ERR63
Intput terminal
Slave 05
From
equipment
Alarm output
Alarm output
Alarm output
ERR51
ERR52
ERR53
Intput terminal
Slave 04
From
equipment
Alarm output
Alarm output
Alarm output
ERR41
ERR42
ERR43
Intput terminal
Slave 01
(Repeater)
Input
terminal
Output
terminal
Line C
5-36