10.2 System Register Settings
10.2.1 System Register Settings (Transistor Output Type)
Functions to be used are allocated in the "System register settings" dialog box. The following
procedure is explained on the condition that the FPWIN GR7 has already started.
1.
Select
Options
>
System register settings
from the menu bar.
The "PLC Configuration" dialog box appears.
2.
Select "Controller input setting 1 (HSC / PLS)" or "Controller input setting 2 (HSC / PLS)"
from the left pane.
The setting menu for the system register “No. 400" or “No. 401” appears.
3.
Change the settings for the channels used for the high-speed counter.
The following figure shows the case when 2-phase input (X0, X1) is allocated to CH0.
4.
Press the [OK] button.
The screen returns to the ladder edit screen. The settings will be downloaded to the PLC
together with programs and comments.
System register relating to high-speed counter output
Classification
No. and setting item
Settings
Control Unit input
settings 1
(HSC / PLS)
400
High-speed counter
setting
(X0 to X3)
CH0
Select either Addition input (X0), Subtraction
input (X0), 2-phase input (X0, X1), Individual
input (X0, X1), or Direction distinction input (X0,
X1).
10.2 System Register Settings
WUME-FPXHPOSG-01
10-7
Summary of Contents for FP-XH Series
Page 2: ... MEMO 2 WUME FPXHPOSG 01 ...
Page 18: ... MEMO 1 10 WUME FPXHPOSG 01 ...
Page 30: ... MEMO 3 8 WUME FPXHPOSG 01 ...
Page 51: ...4 4 Reading Elapsed Values WUME FPXHPOSG 01 4 21 ...
Page 52: ... MEMO 4 22 WUME FPXHPOSG 01 ...
Page 88: ... MEMO 5 36 WUME FPXHPOSG 01 ...
Page 94: ... MEMO 6 6 WUME FPXHPOSG 01 ...
Page 140: ... MEMO 9 8 WUME FPXHPOSG 01 ...
Page 193: ... MEMO WUME FPXHPOSG 01 ...
Page 194: ...Panasonic Industrial Devices SUNX Co Ltd 2020 October 2020 WUME FPXHPOSG 01 ...