2.
Make necessary parameter settings according to the application and press the [OK] button.
The settings will be stored as part of positioning parameter data.
Parameters
Parameter name
Default
(unit)
Settings
Basic
Pulse output method
Pulse/Sign
Pulse/Sign, CW/CCW
Pulse output rotation
direction
CW dir
When selecting Pulse/Sign mode:
CW dir: Select this setting for the case that the
elapsed value is increased when Sign output turns off.
CCW dir: Select this setting for the case that the
elapsed value is increased when Sign output turns on.
When selecting CW/CCW mode:
CW dir: Select this setting for the case that the
elapsed value is increased at the time of CW output.
CCW dir: Select this setting for the case that the
elapsed value is increased at the time of CCW output.
Startup speed
100 (pps)
Set the startup speed common to each operation. This
setting is common to JOG operation, home return, E-point
control, P-point control, C-point control and J-point
control.
Setting range: 1 to 100,000
Positioning repeat count 0
Specify this setting for performing repetitive controls when
using E-point/P-point/C-point control.
4.2 Settings in Configurator PMX
4-10
WUME-FPXHPOSG-01
Summary of Contents for FP-XH Series
Page 2: ... MEMO 2 WUME FPXHPOSG 01 ...
Page 18: ... MEMO 1 10 WUME FPXHPOSG 01 ...
Page 30: ... MEMO 3 8 WUME FPXHPOSG 01 ...
Page 51: ...4 4 Reading Elapsed Values WUME FPXHPOSG 01 4 21 ...
Page 52: ... MEMO 4 22 WUME FPXHPOSG 01 ...
Page 88: ... MEMO 5 36 WUME FPXHPOSG 01 ...
Page 94: ... MEMO 6 6 WUME FPXHPOSG 01 ...
Page 140: ... MEMO 9 8 WUME FPXHPOSG 01 ...
Page 193: ... MEMO WUME FPXHPOSG 01 ...
Page 194: ...Panasonic Industrial Devices SUNX Co Ltd 2020 October 2020 WUME FPXHPOSG 01 ...