7.2 FP-X Compatible Instruction Mode Control Instruction
7.2.1 [F171 (SPDH)] Pulse Output (Trapezoidal Control)
This instruction outputs pulses from a specified pulse output channel according to specified
parameters.
■
Instruction format
■
Operand
Operand
Settings
S
Starting number of the area in which data tables are registered
n
Target channel for pulse output
■
Memory area type that can be specified
Operand
WX
WY
WR
WL
SV
EV
DT
LD
I
Constant
Index
modifier
K
H
S
-
-
-
-
-
-
●
-
-
-
-
●
n
-
-
-
-
-
-
-
-
-
●
●
-
■
Outline of operation
● Outputs pulses from a specified channel when a corresponding control active flag is OFF
and the execution condition is ON.
● The control code, initial speed, maximum speed, acceleration / deceleration time, and target
value are specified by creating data tables [S] to [S+11] described on the next page using a
user program.
● Switches the frequency from the initial speed to the maximum speed in the specified
acceleration / deceleration time. At the time of deceleration, switches the frequency with the
same inclination as that for acceleration.
● For setting the frequency to 50 kHz or more, specify the duty of 1/4 (25%).
■
Operation mode
Incremental <Relative value control>
Outputs the pulses set with the target value.
7.2 FP-X Compatible Instruction Mode Control Instruction
7-10
WUME-FPXHPOSG-01
Summary of Contents for FP-XH Series
Page 2: ... MEMO 2 WUME FPXHPOSG 01 ...
Page 18: ... MEMO 1 10 WUME FPXHPOSG 01 ...
Page 30: ... MEMO 3 8 WUME FPXHPOSG 01 ...
Page 51: ...4 4 Reading Elapsed Values WUME FPXHPOSG 01 4 21 ...
Page 52: ... MEMO 4 22 WUME FPXHPOSG 01 ...
Page 88: ... MEMO 5 36 WUME FPXHPOSG 01 ...
Page 94: ... MEMO 6 6 WUME FPXHPOSG 01 ...
Page 140: ... MEMO 9 8 WUME FPXHPOSG 01 ...
Page 193: ... MEMO WUME FPXHPOSG 01 ...
Page 194: ...Panasonic Industrial Devices SUNX Co Ltd 2020 October 2020 WUME FPXHPOSG 01 ...