Error
code
Name
Opera-
tion
status
Description and steps to take
FP0
FP-e
FP
Σ
FP-X
FP1/FP-M
FP2
FP2SH
FP10SH
FP3
E41
Intelligent
unit error
Selec-
table
An abnormality in an intelligent unit.
FP
Σ
, FP-X:
Check the contetns of special data
register “DT90006” and locate the
abnormal FP intelligent unit (application
cassette for FP-X).
FP2,FP2SH,and FP10SH:
Check the contents of special data
registers DT90006,DT90007 and locate
the abnormal intelligent unit.Then check
the unit referring to its manual..
Selection of operation status using
system register22:
-to continue operation,set 1
-to stop operation,set 0
FP3:
Check the contents of special data
registers DT9006,DT9007 and locate the
abnormal intelligent unit.Then check the
unit referring to its manual..
Selection of operation status using
system register22:
-to continue operation,set 1
-to stop operation,set 0
Verification is possible in FPWIN GR/Pro
at”I/O error” in the status display
function.
A A
A A A A
E42
I/O unit
verify error
Selec-
table
I/O unit(Expansion unit) wiring condition
has changed compared to that at time fo
power-up.
⇒
Check the contents of special data
register (FP0: DT9010,
FP
Σ
, FP-X: DT90010,DT90011) and
locate the erroneous expansion unit.
It checks whether an expansion
connector is in agreement.
⇒
Check the contents of special data
register (FP2,FP2SH,and
FP10SH:DT90010,DT90011,FP3
DT9010,DT9011)
Selection of operation status using
system register23:
-to continue operation,set 1
-to stop operation,set 0
Verification is possible in FPWIN GR/Pro
at”I/O error” in the status display
function.
A
A A
A A A A
A:Available
Summary of Contents for FP E Series
Page 1: ......
Page 16: ......
Page 17: ...Chapter 1 Functions and Restrictions of the Unit ...
Page 28: ...1 12 ...
Page 29: ...Chapter 2 Specifications and Functions of the Unit ...
Page 37: ...2 9 Circuit diagram C32 Y0 Y1 Y3 Y4 C28 Y0 Y1 Y3 Y4 Y2 Y5 to YF Y2 Y5 to YB ...
Page 48: ...2 20 ...
Page 49: ...Chapter 3 Expansion ...
Page 56: ...3 8 Terminal layout diagram Note The numbers in the connector are for the first expansion ...
Page 61: ...Chapter 4 I O Allocation ...
Page 66: ...4 6 ...
Page 67: ...Chapter 5 Installation and Wiring ...
Page 90: ...5 24 ...
Page 91: ...Chapter 6 High speed counter Pulse Output and PWM Output functions ...
Page 116: ...6 26 ...
Page 121: ...6 31 ...
Page 125: ...6 35 Pulse output diagram ...
Page 131: ...6 41 ...
Page 139: ...6 49 ...
Page 141: ...6 51 ...
Page 144: ...6 54 Program Continued on the next page ...
Page 145: ...6 55 ...
Page 147: ...6 57 Program ...
Page 151: ...Chapter 7 Communication Cassette ...
Page 210: ...7 60 The values of DT50 and DT51 are written in DT0 and 1 of PLC ...
Page 238: ...7 88 ...
Page 239: ...Chapter 8 Self Diagnostic and Troubleshooting ...
Page 247: ......
Page 248: ......
Page 249: ...Chapter 9 Precautions During Programming ...
Page 260: ...9 12 Example 2 Using the CT instruction between JP and LBL instructions ...
Page 268: ...9 20 ...
Page 269: ...Chapter10 Specifications ...
Page 286: ......
Page 287: ...Chapter 11 Dimensions ...
Page 290: ...11 4 11 1 3 Expansion Unit FPG XY64D2T FPG XY64D2P FPG EM1 ...
Page 293: ...Chapter 12 Appendix ...
Page 297: ...12 5 ...
Page 437: ...12 145 12 7 ASCII Codes ...
Page 439: ......
Page 440: ......