7-72
Setting the largest unit number for a PC(PLC) link
The largest unit number can be set using system register no. 47 (using system register no. 57 for
PC(PLC) link 1 (for FP
Σ
32k type only)).
[Sample setting]
No. of units linked
Setting contents
2
1st unit: Unit no. 1 is set
2nd unit: Unit no. 2 is set
A largest unit no. of 2 is set for each.
4
1st unit: Unit no. 1 is set
2nd unit: Unit no. 2 is set
3rd unit: Unit no. 3 is set
4th unit: Unit no. 4 is set
A largest unit no. of 4 is set for each.
n
Nth unit: Unit no. n is set
A largest unit no. of n is set for each.
Note:
•
Unit numbers should be set sequentially and consecutively, starting from 1, with no breaks between
them. If there is a missing unit number, the transmission time will be longer.
•
For all PLCs which are linked, the same value should be set for the largest unit number.
•
If there are fewer than 16 units linked and the largest unit number has not been set (default=16), or the
largest unit number has been set but the unit number settings are not consecutive, or the unit number
settings are consecutive but there is a unit for which the power supply has not been turned on, the
response time for the PC(PLC) link (the link transmission cycle) will be longer.
Reference:
<7.6.5 PC(PLC) Link Response Time>.
Setting PC(PLC) link switching flag (For FP
Σ
32k type only)
PC(PLC) link switching flag can be set using system register no. 46.
If it is set to 0 (default value), the first half of the link relays and registers are used. If it is set to 1, the
second half of the loink relays and registers are used.
Summary of Contents for FP E Series
Page 1: ......
Page 16: ......
Page 17: ...Chapter 1 Functions and Restrictions of the Unit ...
Page 28: ...1 12 ...
Page 29: ...Chapter 2 Specifications and Functions of the Unit ...
Page 37: ...2 9 Circuit diagram C32 Y0 Y1 Y3 Y4 C28 Y0 Y1 Y3 Y4 Y2 Y5 to YF Y2 Y5 to YB ...
Page 48: ...2 20 ...
Page 49: ...Chapter 3 Expansion ...
Page 56: ...3 8 Terminal layout diagram Note The numbers in the connector are for the first expansion ...
Page 61: ...Chapter 4 I O Allocation ...
Page 66: ...4 6 ...
Page 67: ...Chapter 5 Installation and Wiring ...
Page 90: ...5 24 ...
Page 91: ...Chapter 6 High speed counter Pulse Output and PWM Output functions ...
Page 116: ...6 26 ...
Page 121: ...6 31 ...
Page 125: ...6 35 Pulse output diagram ...
Page 131: ...6 41 ...
Page 139: ...6 49 ...
Page 141: ...6 51 ...
Page 144: ...6 54 Program Continued on the next page ...
Page 145: ...6 55 ...
Page 147: ...6 57 Program ...
Page 151: ...Chapter 7 Communication Cassette ...
Page 210: ...7 60 The values of DT50 and DT51 are written in DT0 and 1 of PLC ...
Page 238: ...7 88 ...
Page 239: ...Chapter 8 Self Diagnostic and Troubleshooting ...
Page 247: ......
Page 248: ......
Page 249: ...Chapter 9 Precautions During Programming ...
Page 260: ...9 12 Example 2 Using the CT instruction between JP and LBL instructions ...
Page 268: ...9 20 ...
Page 269: ...Chapter10 Specifications ...
Page 286: ......
Page 287: ...Chapter 11 Dimensions ...
Page 290: ...11 4 11 1 3 Expansion Unit FPG XY64D2T FPG XY64D2P FPG EM1 ...
Page 293: ...Chapter 12 Appendix ...
Page 297: ...12 5 ...
Page 437: ...12 145 12 7 ASCII Codes ...
Page 439: ......
Page 440: ......