EBL512 G3 V. 3.0.X
- FIRE ALARM SOLUTIONS OPERATING INSTRUCTIONS
80
23.4. MAKE TWO NETWORKS ONE
a) Make sure the system properties is the same in the two systems.
b) Make sure that no presentation numbers in the systems are the same as another.
c) Choose one of the systems as starting point, for example the largest system, and add the control units and all other units from
the other system.
It is very important that two or more presentation numbers (Zone or Zone-Address) in the systems are not
the same.
It is not possible to merge two networks into one or copy one system and paste into another system.
If it is known from the beginning that two systems shall be one in the future, it is possible to give the control units in the system
respectively, the "final" control unit numbers right from the beginning in order to get the correct technical numbers in the system
documents.
23.5. DELETE A CONTROL UNIT IN A NETWORK
a) Physically disconnect the control unit. This action will generate faults in the other control units.
b) Acknowledge the faults.
c) Open the SSD for the current system via EBLWin. Delete the control unit (and the units connected to it) and download the
new SSD.
TLON NETWORK:
d) Open the current project in TLON Manager, delete the control unit according to the separate Technical description
MEW01983.