5.4. INFORMATION PRIORITY ORDER
When the control unit / system is in normal operation (quiescent state), which means no fire alarms, no faults, no disablements, no
service signals, no zones in test mode, no activated interlocking in / outputs, and/or Alert Annunciation function not enabled, only the
LED "Operation" should be lit and some system information is shown in the control unit display. However, the system information
has the lowest priority and more important information suppresses less important. In some cases also valid for the symbol area.
PRIORITY ORDER TABLE
Priority Event
Symbol area is visible
1
Fire alarms:
• Fire alarm
• Heavy smoke/heat alarm
• Alert Annunciation (AA) alarm
• Key cabinet alarm
No
2
Quiet alarm
No
3
Co-incidence alarm
No
4
Delayed alarm
No
5
Pre-warning
No
6
Test mode alarm
No
7
LAA alarm
Yes
8
Evacuate information
Yes
9
Fault
Yes
10
Disablement
Yes
11
Zones in "Test mode"
Yes
12
Interlocking input / output active
Yes
13
System information
Yes