EBL512 G3 V. 3.0.X
- FIRE ALARM SOLUTIONS OPERATING INSTRUCTIONS
28
Zone numbers 001-999 can be used, but in accordance with the EN54-2 standard not more than 512 alarm
points and/or zones can be used per c.i.e.
10. PRESENTATION NUMBER
For each fire alarm point / input / zone, a presentation number, NNN-NN, has to be programmed. The presentation number is shown
in the c.i.e. display and the external display units, to identify the point / zone activating fire alarm.
It is also used to disable / re-enable fire alarm points / zones and as trigger conditions in control expressions to activate programma
-
ble outputs.
Together with the presentation number, a user definable 40 characters text message (alarm text) can be displayed (if programmed).
NNN
NN
001-999
00-99
Zone number
01 – 99 = The address within the zone.
00 = Only the zone number will be
displayed, e.g. used for conventional zone
line inputs.