EBL512 G3 V. 3.0.X
- FIRE ALARM SOLUTIONS OPERATING INSTRUCTIONS
55
• In the c.i.e. display up to three fault messages can be shown simultaneously. In the display, down to the left, is displayed the
number of faults.
• If a fault has been corrected (serviced) before it has been acknowledged, the status information is "/Serviced", see above.
• Fire alarm presentation has higher priority than the fault messages, however during fire alarm presentation the faults can be
shown via the menu system, see section
ENTERING THE MENUS DURING FIRE ALARM
Faults have to be acknowledged, which is done via menu H6, see chapter
on page 113. This menu
is a list of all faults in the system:
• not corrected / serviced and not acknowledged fault
• not corrected / serviced but acknowledged fault
(/Acknowledged)
• corrected / serviced but not acknowledged fault
(/Serviced)
If a fault cannot be corrected, it is important to contact service personnel / engineer immediately.
The faults are normally latched, but can via EBLWin be set to be "not latched". This will make the fault disappear from the list when
serviced but not acknowledged.
The fault list shown when the user is logged out of the menu, displays all faults, even acknowledged faults.
As a reminder, faults (and disablements) are indicated by a 2-sec. beep when an open c.i.e. door is being
closed.