30. PRESENT SYSTEM STATUS (H4)
If a printer is mounted (an option for control unit 5000), it is possible to get a print-out from some of the menus. In this case, the soft
key "Print" shall be used.
During printing "Print" will be replaced with "Abort printing". When "Abort printing" is pressed the soft key
text immediately changes back to "Print" but the items already stored in the print buffer will be printed (up
to five items).
a) Log on to the c.i.e.
b) Navigate to menu H4.
c) Press
. A sub menu list (U1 – U8) will be displayed.
30.1. DISABLEMENT (H4/U1)
This is a dynamic list of all disablements in the system. Also alarm point(s) and/or zones disabled via
on page 52 are shown in the list.
If there are no disablements --List is empty-- will be shown.
a) Log on to the c.i.e.
b) Navigate to menu U1.
c) Scroll in the list with
.
d) To exit the menu press ESC
.
Disablements by time channels are listed in this menu, but not with detailed information about zone and
zone address, see example below. For more information, see menu H4/U2.
Alarm points disabled by time channel in control unit
XX yyyy-mm-dd hh:mm
Disablement 2 of 2
Zone XXX address XX disabled
yyyy-mm-dd hh:mm
Zone XXX is disabled
Automatic re-enable hh:mm
yyyy-mm-dd hh:mm
Disablement 1 of 2