EBL512 G3 V. 3.0.X
- FIRE ALARM SOLUTIONS OPERATING INSTRUCTIONS
117
If a sensor 430x, 4400 and 4401 in NORMAL mode is replaced without having generated service signal, it
has to be reset to the default week average sensor value via menu CLEAR WEEKLY AVERAGE (H8/S3).
34.2. ACKNOWLEDGE SERVICE SIGNAL (H8/S2)
When SERVICE signal is generated in the system, following symbol is shown in the display's symbol area:
30.5. SENSORS ACTIVATING SERVICE SIGNAL (H4/U5)
Sensor
= analog smoke detector.
Only 430x, 4400 and 4401 sensors in NORMAL mode have to be acknowledged: When service signal from such a sensor is ac
-
knowledged, the sensor is given a default week average sensor value (same as for a new / clean sensor = 0.1 %/m). First replace
the sensor and then acknowledge the service signal as soon as possible. The first week average sensor value after acknowledge
will be calculated within one hour, then each week.
Sensors 4400, 4401 set in advanced mode and 4402 (always set in normal mode) do not have to be acknowledged if they are
replaced after generating service signal. They will be automatically reset.
a) Log on to the c.i.e.
b) Navigate to menu S2.
c) Press or to scroll in the list:
d) To acknowledge a sensor, select it and press
. The acknowledged sensor disappears from the list.
e) To exit the menu press ESC
.
If there are no sensors ---List is empty--- will be shown.
The most recent service signal is on top of the list. A serviced fault that is acknowledged will disappear from this list.
The "Service symbol"
will be turned off when all sensors have been acknowledged.
Previous
page
Sensor, Zone ZZZ address AA needs service
technical address xxxxxx
2019-12-03 09:09:15
Sensor, Zone XXX address AA needs service
technical address xxxxxx
2019-11-03 19:09:35
Fault 1/2 is selected
Next
page