EBL512 G3 V. 3.0.X
- FIRE ALARM SOLUTIONS OPERATING INSTRUCTIONS
108
31.5. DISPLAY CURRENT CONSUMPTION ON COM-LOOP (H5/A5)
The current consumption (an average value) for each COM loop can be displayed.
a) Log on to the c.i.e.
b) Navigate to menu A5.
c) Write loop number and control unit number and press
.
d) Please wait.
No or very small current consumption (< 10 mA) cannot be presented correctly / precisely since the accu
-
racy is ±5 mA.
If you get “No reply from control unit.....” the control unit don't exist or don't answer.
e) To exit the menu press
or ESC
.
The information is automatically updated every 5th second.
Current consumption and resistance on COM-loop: 0
control unit 00
COM-loop 0
xxxx mA ≤ xxx Ω
SUB-loop 0
xxxx mA ≤ xxx Ω