- FIRE ALARM SOLUTIONS OPERATING INSTRUCTIONS
90
28.1. ZONE OR ZONE/ADDRESS (H2/B1)
When a whole zone is disabled, all alarm points within the zone will be disabled except the addressable manual call points.
Alarm points can be individually disabled.
DISABLE:
a) Log on to the c.i.e.
b) Navigate to menu B1
c) Press the soft key
Change type of disablement
to toggle between:
-
Zone
000
-
Zone
000
address
00
-
Zone
000
address
00 `Smoke only`.
d) If "Automatically re-enablement" shall be used, time press and . Insert time (hh:mm). Default is current time + 3 hours.
e) Press
to disable.
RE-ENABLE:
f) Use the
to toggle between:
-
Disable
-
Re-enable list
g) Select “Re-enable list”.
h) Press to select the Zone or Zone / Address to be re-enabled.
i) Press
to re-enable. Re-enabled zone or zone / address will disappear from the list, indicated with a beep.
The sensor values for disabled analog smoke detectors in NORMAL mode will not be used for calculation
of the week average sensor value, i.e. only the values saved before and after the disablement will be used
for this calculation.