EBL512 G3 V. 3.0.X
- FIRE ALARM SOLUTIONS OPERATING INSTRUCTIONS
58
FAULT: Alert annunciation unit xx,
Channel x, CU xx
5054 (Alert Annunciation Unit - AAU.)
The AAU unit xx, connected to channel x, control unit no. xx, is programmed as another type in the SSD or a fault in the unit.
FAULT: Alert annunciation unit xx,
control unit xx
5054 (Alert Annunciation Unit - AAU.)
The AAU unit xx, connected to control unit no. xx, is programmed as another type in the SSD or a fault in the unit.
FAULT: Aspect not calibrated zone xxx
address xx
The Aspiration smoke detector Aspect Lazeer is not working as it should be, i.e. the unit has not been calibrated in conjunction
with commissioning.
FAULT: Aspect not calibrated zone xxx
address xx and zone xxx address xx
The Aspiration smoke detector Aspect Nitro / Grizzle is not working as it should be, i.e. the unit has not been calibrated in
conjunction with commissioning.
FAULT: Aspect zone xxx address xx
Check the specified Aspiration smoke detector Aspect Lazeer. (One detection area, one or two pipelines per detection area.)
FAULT: Aspect zone xxx address xx and
zone yyy address yy
Check the specified Aspiration smoke detector Aspect Nitro / Grizzle. (Two detection areas, one or two pipelines per detection
area.)
FAULT: Battery not connected,
control unit xx
• Battery voltage is below 18.9 V.
• Batteries (2 x 12 V) are missing or not connected correctly.
• Fuse F2 on the main board is blown.
• Other / external battery fuse is blown.
This check is done every 14th minute but when the fault is generated the check is done every 30th sec.
Fuse: F6.3AH 250V (5x20 mm ceramic).
FAULT: Battery, technical number xxxxxx
The charging function in the external power supply 3366 or 4466 connected on the COM loop is not OK.
• Batteries (2 x 12 V) are missing or not connected correctly.
• The PCB is faulty and has to be replaced.