EBL512 G3 V. 3.0.X 

 - FIRE ALARM SOLUTIONS OPERATING INSTRUCTIONS

97

30.2.  DISABLEMENT BY TIME CHANNEL (H4/U2)

This is a static list of all disablements by time channels in the system. The list has up to four items per page. Indicated by LED 

"General disablements".

a)  Log on to the c.i.e.

b)  Navigate to menu U2.

c)  Scroll in the list with   

.

30.3.  OPEN DOORS (H4/U3)

If any door in the system is open the following symbol is shown in the display: 

 

See also chapter 

17. OPEN DOOR

 on page 35

.

This menu is a dynamic list of all open doors in the system.

a)  Log on to the c.i.e.

b)  Navigate to menu U3.

c)  Scroll in the list with   

.

Zone XXX address XX disabled by time

Channel

Zone XXX address YY disabled by time

channel.

Number of disablement by time channel: 2

d)  To exit the menu press ESC

.

d)  To exit the menu press ESC

.

All other disablements are listed in menu H4/U1.

Door open control unit 00

yyyy-mm-dd  hh:mm

Door open control unit 01

fire brigade panel 00

yyyy-mm-dd  hh:mm

Open door 1 of 2

Summary of Contents for EBL512 G3 5000

Page 1: ...EBL512 G3 V 3 0 X Fire alarm solutions 5000S Series OPERATING INSTRUCTONS www panasonic fire security com...

Page 2: ...ON 19 6 USER DATA 20 6 1 USER NAME 20 6 2 PASSWORD 21 6 2 1 CHANGE OF PASSWORD 21 6 2 2 PASSWORD FOR GATEWAY ACCESS ONLY 21 7 ACCESS 22 7 1 HOW TO LOG ON 22 7 2 NAVIGATION GENERAL PROCEDURES 22 8 USER...

Page 3: ...RM 48 18 2 ALARM SOURCE 49 19 ALARM RESET 50 19 1 PRE WARNING RESET 50 19 2 FIRE ALARM RESET 50 19 2 1 ALL 50 19 2 2 SINGLE 51 19 2 3 SINGLE WITH AUTOMATIC DISABLEMENT 52 19 3 TEST MODE ALARM 52 19 4...

Page 4: ...0 1 DISABLEMENT H4 U1 96 30 2 DISABLEMENT BY TIME CHANNEL H4 U2 97 30 3 OPEN DOORS H4 U3 97 30 4 SENSOR VALUES H4 U4 98 30 4 1 EXPLANATION TO THE SENSOR VALUES 99 30 5 SENSORS ACTIVATING SERVICE SIGNA...

Page 5: ...5 1 AFTER RESTART 121 34 6 ACTIVATE ADDRESS IN ALARM MODE H8 S6 122 34 7 SYNCHRONIZE THE CONTROL UNITS H8 S7 123 34 8 ACTIVATE RESET OUTPUTS H8 S8 124 35 INTERLOCKING OUTPUTS AND INPUTS H9 125 35 1 A...

Page 6: ...t to change without notice as are other technical features and data More information on characteristics mounting connections and technical data for the control unit and all other units is found in eac...

Page 7: ...article number Example of a product name EBL512 G3 CU 512 alarm points with printer Hardware HW for example a printed circuit board PCB has a type number an article number a product name a PCB number...

Page 8: ...A unit with a built in address device Each unit is individually identified handled and indicat ed in the Control Unit The unit can be an I O unit with a zone line input to which one or more conventio...

Page 9: ...alarm presentation etc for the fire brigade personnel Can be a part of the control unit a part of the front or a separate Display Unit external FBP In an ext FBP a printer can be included Display LCD...

Page 10: ...to 512 can be alarm points according to EN54 2 EBL512 G3 can be used as a stand alone control unit or connected to a network A network can have up to 30 control units EBL512 G3 is available in several...

Page 11: ...an older S W version in the new control unit The same S W version is required in all control units in a network EBLWin The PC program EBLWin is used for programming and commissioning of one or more c...

Page 12: ...ts for routing equipment Fire alarm output for Fire brigade tx and Fault condition output for Fault tx Connectors for two network boards 5040 5090 One RS485 and 24 V DC outputs for Display units 5054...

Page 13: ...on how alarm points zones having activated fire alarm In the middle part will the fire alarms be shown one alarm point or one zone together with user definable alarm text if programmed 5 2 CONTROL PA...

Page 14: ...IRE ALARM SOLUTIONS OPERATING INSTRUCTIONS 14 5 3 DETAILED DESCRIPTION OF THE FRONT Menu Next zone Re enable Evacuate 2 3 4 5 6 7 8 9 10 28 27 26 17 18 21 11 12 13 14 15 16 29 30 31 32 33 22 35 34 34...

Page 15: ...to scroll amongst the zones 7 System fault EBL512 G3 is not running because of S W fault CPU fault Memory fault No contact between main board and MMI board C i e restart fault code 00 03 25 50 53 8 G...

Page 16: ...s or zone addresses See also 18 1 2 FIRE ALARM on page 38 NOTE To scroll browse through the queued zones use the soft key Next zone 23 22 25 Soft keys The function is shown in the display above the so...

Page 17: ...for one or more analog smoke detectors in the system See also menu 30 5 SENSORS ACTIVATING SERVICE SIGNAL H4 U5 on page 100 Symbol flashing The system is in service mode A COM loop is disconnected A C...

Page 18: ...shown in the control unit display However the system information has the lowest priority and more important information suppresses less important In some cases also valid for the symbol area PRIORITY...

Page 19: ...L512 G3 When the Russian Ukraine Australian or the New Zealand language is selected the date is shown as follows dd mm yyyy yyyy mm dd Date Year Month Day Control Unit XX 00 29 hh mm Time hour minute...

Page 20: ...r names and passwords will be valid 6 USER DATA EBL512 G3 has different user levels for different kind of users To log on to an EBL512 G3 a user name and a password are re quired Ten different User na...

Page 21: ...password via menu H10 If the valid password s are unknown EBLWin must be used to change the password s CHANGE VIA MENU H10 See chapter 36 CHANGE PASSWORD H10 on page 128 6 2 2 PASSWORD FOR GATEWAY ACC...

Page 22: ...0 Information only no password is required NO ACCESS No access will be shown if the password was not correct Try again 7 2 NAVIGATION GENERAL PROCEDURES Scroll in lists or menus with Press to toggle...

Page 23: ...utputs and inputs H10 Change password 8 1 USER LEVEL ACCORDING TO EN54 2 User level EN54 2 User level type Required action equipment Access to 1 No Hole in the Plexiglas Alarms queued button 2A Fire b...

Page 24: ...has been opened with the fire brigade key Door open symbol in the symbol area you have access to level 2A and after log on as Information only level 2B access to the following menus H4 Present system...

Page 25: ...B3 Output type B4 Alarm devices B5 Routing equipment B6 Alert annunciation function H3 Set calendar and clock H4 Present system status U1 Disablement U2 Disablement by time channel U3 Open doors U4 Se...

Page 26: ...DU A8 Setup wireless detectors A9 SSD information H8 Maintenance S1 Dis Re connect loop zone line input S2 Acknowledge SERVICE signal S3 Clear weekly average S4 Test of alarm devices S5 Safe shut down...

Page 27: ...Manager COM loop number The technical address on the COM loop The addresses don t have to be in sequence The connections on the COM loop don t have to be in sequence The address for each unit is set...

Page 28: ...umber is shown in the c i e display and the external display units to identify the point zone activating fire alarm It is also used to disable re enable fire alarm points zones and as trigger conditio...

Page 29: ...ounder base 3379 4479 Light indicator 4383 Wireless smoke detector 4611 and all alarm devices 448X If the push button Silence alarm devices is pressed again the sounders will automatically sound again...

Page 30: ...m device for a specified control unit or all control units can be activated for an alarm device test 12 DISABLE OR RE ENABLE ALARM DEVICES Outputs programmed for sounders can be collectively disabled...

Page 31: ...ocking input 0 8 0 8 sec if this option is selected via EBLWin Activated technical warning 0 5 10 sec if this option is selected via EBLWin PRESS SILENCE BUZZER TO SILENCE THE BUZZER In case of a new...

Page 32: ...Loop unit xxxxxx output x Control unit xx Sx Control unit xx Rx Control unit xx expansion board x output x This is indicated by LED Fault Disablements General disablements They will remain disabled u...

Page 33: ...ied control unit or all control units This is indicated by LED Fault Dis ablements General disablements They will remain disabled until they are re enabled again via menu H2 B3 See also section 34 8 A...

Page 34: ...type Alarm devices for evacuation will be disabled by H2 B4 The sounders will remain turned ON until they are turned OFF by pressing the soft key Evacuate off or alternatively when the programmable in...

Page 35: ...switch None selected by default Open door in a C U will not disable the output s for routing equipment Fire brigade tx and fault tx Any control unit door Open door in any C U will disable the output s...

Page 36: ...tected by a smoke detector without activating a fire alarm in the system If the Local Alarm Acknowledgement function is used there will be an indication in the c i e display during the Acknowledgement...

Page 37: ...ble text message the alarm text for fire alarm is shown if programmed Example pre warning zone 123 address 45 within zone 123 Menu 123 45SMOKE Zone Address User definable alarm text for 123 45 Pre war...

Page 38: ...c each 0 4th sec 0 4 0 4 sec LEDs Fire L1 are blinking 0 4 0 4 sec Output for routing equipment Fire brigade tx is activated In case of Selective alarm presentation only for the selected alarms Output...

Page 39: ...be used ADDITIONAL INFORMATION First alarm Latest alarm Alarm number and number of zones in alarm LEDs Alarms queued blinking 0 4 0 4 sec are indicating that more than one fire alarm is activated To s...

Page 40: ...ber 1 of 1 Fire alarm 002 03 Latest alarm 003 11 Escape menu H1 Perform monthly test H2 Disable or re enable H3 Set calender and clock H4 Present system status H5 Service H6 FAULT Acknowledge H7 Perfo...

Page 41: ...page 114 When an alarm point in a zone set in test mode is tested it is presented in the display as a fire alarm but with the information Test mode added If a printer is available the test mode alarm...

Page 42: ...HAPPENS IN CASE OF A HEAVY SMOKE HEAT ALARM Outputs programmed for heavy smoke heat alarm are activated General heavy smoke heat alarm and individual alarm points zones Each heavy smoke heat alarm is...

Page 43: ...ire alarm informa tion The AA alarm has to be acknowledged within an acknowledge time and reset within an investigation time otherwise the out put s for routing equipment fire brigade tx will be activ...

Page 44: ...If the key cabinet is opened without a fire alarm for example if somebody illegally breaks into the key cabinet a key cabinet alarm will be activated An example XX Control Unit number 00 29 Menu Alarm...

Page 45: ...ne zone or one zone address alarm point is in alarm status the c i e buzzer sounds 0 8 5 sec and there is a Coincidence alarm presentation in the display Note that LEDs Fire are not indicating a co in...

Page 46: ...d In case of a Delayed alarm the following happens The buzzer in the c i e sounds 0 8 sec each 5th sec 0 8 sec 5 sec In the c i e display a presentation number zone address is shown for the first dela...

Page 47: ...hnical description MEW01838 for more information During the Acknowledgement Period 10 120 sec the following information a list if many is shown in the c i e display During the Investigation Period 1 9...

Page 48: ...are turned on i e also a connected ext LED The buzzer sounds 0 8 5 sec and there is a Quiet alarm presenta tion including a title Quiet alarm in the display Menu 123 45SMOKE Zone Address User definabl...

Page 49: ...fire alarm Each fire alarm is presented with a title which means that the alarm source Smoke Heat Multi or MCP will be added to the normal fire alarm information Menu 002 03SMOKE Zone Address User def...

Page 50: ...press Enter and hold them pressed for 0 5 sec 19 2 1 ALL All activated fire alarms alarm points zones will be reset by pressing Reset once This is in accordance with the EN54 2 standard When all fire...

Page 51: ...ueued are lit the next fire alarm in the queue will be shown in the mid dle of the display It has to be reset the same way as the first one When all fire alarms are reset LEDs Fire and Alarms queued a...

Page 52: ...alarm status will not only be reset but also disabled which means it will not activate a new fire alarm It has to be re enabled via menu H2 B1 before it can activate a new fire alarm This function se...

Page 53: ...arm point zone is no longer in alarm state See also chapter 18 1 6 CO INCIDENCE ALARM 2 ADDRESS ZONE DEPENDENCE on page 45 19 8 DELAYED ALARM The Delayed alarm will be automatically reset if the alarm...

Page 54: ...ppressed buzzer during fault is set via EBLWin The fault condition output for routing equipment Fault tx will be activated Programmable output s for general fault will be activated and output s for ge...

Page 55: ...ged which is done via menu H6 see chapter 32 FAULT ACKNOWLEDGE H6 on page 113 This menu is a list of all faults in the system not corrected serviced and not acknowledged fault not corrected serviced b...

Page 56: ...AU xx Secondary channel CU xx FAULT 24V for FBP xx Secondary channel CU xx FAULT 24V for EPU xx Secondary channel CU xx FAULT 24V for GCP xx Secondary channel CU xx The AAU FBP EPU GCP unit xx connect...

Page 57: ...le CU xx xx 00 29 The auto resettable fuses PTC9 and PTC10 total max 1A has been activated Check for overload or damage on the MMI board To reset the PTC disconnect the MMI board and wait 5 min to let...

Page 58: ...it should be i e the unit has not been calibrated in conjunction with commissioning FAULT Aspect zone xxx address xx Check the specified Aspiration smoke detector Aspect Lazeer One detection area one...

Page 59: ...um MMI program control unit xx A fault in the control unit xx main board software LED System fault is turned on This is a very serious fault Call for service personnel engineer immediately FAULT Check...

Page 60: ...smoke detector 4611 has been removed from its base or the door on a wireless manual call point 4614 has been opened FAULT Display units mixed on channels Primary Secondary CU xx The primary and secon...

Page 61: ...programmable input in control unit no xx FAULT External power supply control unit xx The fault is to be found in the external power supply equipment which has a fault output connected to a programmab...

Page 62: ...BP xx connected to control unit no xx is programmed as another type in the SSD or a fault in the unit FAULT Fire brigade panel xx channel x CU xx 5054 Ext Fire Brigade Panel FBP The ext FBP xx connect...

Page 63: ...o 2 8 A 6 3 A again FAULT High resistance sub loop x loop x CU xx The loop resistance measured by the control unit 4585 board is too high for the current consumptions Check cables connec tions etc The...

Page 64: ...500 m The battery might be too old Cables fuses etc for externally placed batteries might cause a voltage drop Check adjust the rectifier power supply voltage 24 V DC Check the charging voltage over...

Page 65: ...s detected the log is saved to flash automatically in order to keep the log intact after a power failure FAULT Low voltage technical number xxxxxx System voltage 21 V DC in the external power supply u...

Page 66: ...the COM loop The fault is activated after 1 300 minutes after Loss of mains i e no 230 V AC to the 4466 unit Blown mains fuse Fuse F1 blown on the 4466 unit s charger board Fuse T5AH 250 V 5x20 mm The...

Page 67: ...interrupted Check the cable all connections etc on the primary channel Is correct complete SSD downloaded via EBLWin Check the address and SW mode settings FAULT No reply AAU xx Secondary channel CU...

Page 68: ...the cable all connections etc Is correct complete SSD downloaded via EBLWin Check the address and SW mode settings FAULT No reply Loop unit xxxxxx The unit e g a customized unit cannot be found by the...

Page 69: ...isted FAULT Printer control unit xx This is valid for an EBL512 G3 type 5000 with printer Control unit no xx Faulty printer Printer not correctly connected No paper Printer selected in EBLWin but no p...

Page 70: ...c This could also mean a faulty 5040 board in either of the two control units listed FAULT Sensor zone xxx address xx technical number xxxxxx The analog smoke heat or multi detector is faulty The dete...

Page 71: ...ol Panel There is no SSD Site Specific Data downloaded to the unit or something is wrong in the downloaded SSD FAULT SSD alert annunciation unit xx Channel x CU xx FAULT SSD external presentation unit...

Page 72: ...input x in the control unit xx Check the cables connections cut off or short circuit FAULT Supervised output x control unit xx If the output is programmed for sounders type Alarm devices it is also i...

Page 73: ...ak on the connected cable equipment Blown fuse F1 Output 0 or F2 Output 1 on the 4583 board Fuse T200mA L 250V TR5 Connected equipment might be missing End of line resistor s missing or not correct va...

Page 74: ...a stored that is not the same in all control units If a control unit restarts in conjunc tion with this fault synchronization will start automatically otherwise synchronization has to be started via m...

Page 75: ...tipurpose I O unit 3361 4461 monitored zone line input Z Break on the zone line or wrong no end of line capacitor 10 F or short circuit if not programmed for fire alarm at short circuit No contact wit...

Page 76: ...0025 alarm text 2021 04 03 15 22 Serviced FAULT No reply zone 123 address 03 technical number 000027 alarm text 2021 04 07 09 25 Acknowledge Number of faults in system 5 See also chapter 32 FAULT ACKN...

Page 77: ...hall be connected to a household removable fuse for the fire alarm c i e only via a two way circuit breaker National regulations always must be followed The mains cable shall be securely clamped and t...

Page 78: ...this system After the control unit ID has been set each control unit will automatically restart and start using the new ID f Download the SSD 23 2 2 TLON NETWORK a Mount the TLON connection board on...

Page 79: ...twork no 1 and the same proce dure as for Network no 0 is done for Network no 1 23 3 ADD A CONTROL UNIT INTO A NETWORK When adding a new control unit to a running installation you must have the same s...

Page 80: ...opy one system and paste into another system If it is known from the beginning that two systems shall be one in the future it is possible to give the control units in the system respectively the final...

Page 81: ...w control unit in the network ring see section 16 3 7 SYSTEM PROPERTIES PAGE 4 in Planning Instructions for this system If you wish to upgrade the number of alarm points a PC and EBLWin are used The P...

Page 82: ...lue is stored in the memory of the real time clock i e the value will be retained also after the c i e has been powered off de energized After any restart a new week average sensor value will be calcu...

Page 83: ...ort auto boot mode FFD WASV SSD S W SSW 15 Automatically due to some external disturbance If this happens call for service personnel engineer Depending on the restart reason also the SSW might be dele...

Page 84: ...ing text message will be shown in the display and the buzzer will sound Regarding code xx and address yyyyyy see section 25 2 RESTART TABLE on page 83 This fault is also indicated by LEDs Rout ing equ...

Page 85: ...BLWin Gateway or via another unit in the system No contact with Main board This is also indicated by LED System fault and the buzzer sounds steady continuous The Fault tx output is activated A new dow...

Page 86: ...g ten 10 chapters describe the menus in the c i e and the procedures to use them There are different access levels for different menus See chapter 8 USER LEVELS on page 23 For general information on n...

Page 87: ...x activated After 30 seconds also the c i e Fire brigade tx output and corresponding programmable outputs type routing equipment will be activated indicated by the LED Fire brigade tx After another 30...

Page 88: ...sting time any time delay for the detectors zones in test mode will be disabled i e fire alarm will be detected faster than normally In the tested alarm point the LED will light up approximately 10 se...

Page 89: ...bled via menu H2 B1 Up to 200 alarm points zones address can be individually disabled via menu H2 B1 Alarm points disabled via time channels are not limited and must not be counted Up to 200 outputs c...

Page 90: ...s 00 Smoke only d If Automatically re enablement shall be used time press and Insert time hh mm Default is current time 3 hours e Press to disable RE ENABLE f Use the to toggle between Disable Re enab...

Page 91: ...not exist Disabled output Even if its control expression trigger condition is fulfilled true the output will not be activated DISABLE a Log on to the c i e b Navigate to menu B2 c Press the soft key C...

Page 92: ...d outputs are listed in menu H4 U1 from which it is also possible to get a print out DISABLE a Log on to the c i e b Navigate to menu B3 c Press the soft key Change type of disablement to toggle betwe...

Page 93: ...5 ROUTING EQUIPMENT H2 B5 Disabled outputs are listed in menu H4 U1 from which it is possible to get a print out Outputs for routing equipment fire brigade tx and fault tx can be disabled and re enabl...

Page 94: ...ed always on Via this menu H2 B6 it is possible to disable the AA function i e the AA function will be turned off for the alarm points zones programmed for Alert Annunciation in spite of the time chan...

Page 95: ...faults etc will be correct The calendar and clock can be set in any c i e for the whole system Every day at midnight the calendar and clock will be syn chronised a Log on to the c i e b Navigate to m...

Page 96: ...displayed 30 1 DISABLEMENT H4 U1 This is a dynamic list of all disablements in the system Also alarm point s and or zones disabled via 19 2 3 SINGLE WITH AUTO MATIC DISABLEMENT on page 52 are shown in...

Page 97: ...n the following symbol is shown in the display See also chapter 17 OPEN DOOR on page 35 This menu is a dynamic list of all open doors in the system a Log on to the c i e b Navigate to menu U3 c Scroll...

Page 98: ...Min XX C Algorithm XX Max XX C Sensor 001 01 technical address 000001 Momentary XX X m Weekly XX X m Perf factor X XX m Min XX X m Algorithm Xxxxxx Max XX X m Momentary XX C Min XX C Max XX C Sensor 0...

Page 99: ...tor s EEPROM i e that value will be used after the detector has been pow erless The Weekly value for the 440x detectors in Advanced mode is also called the Contamination Compensation Value CCV Perform...

Page 100: ...signal from an Analog multi detector with CO 4402 can also indicate that the CO sensor s life time 5 years is reached and the detector has to be replaced Service signal from an Aspirating smoke detec...

Page 101: ...ample CU00 see below can instead be EBLWin EBLWeb or Ext External system no connected via Gateway a Log on to the c i e b Navigate to menu U7 c Press or to scroll between Alarm log Interlocking log Ge...

Page 102: ...arts on 000 and goes to 999 It can be reset to 000 via EBLWin Control unit menu Reset alarm counter The value will be retained also after the c i e has been completely powerless During synchronization...

Page 103: ...t A1 A9 will be displayed Some tasks for Service technicians are done via EBLWin Via PC and EBLWin you can download backup upload the site specific data SSD create and download software S W settings c...

Page 104: ...ll be generated a Log on to the c i e b Navigate to menu A1 c Press to start calibration of supervised outputs d Press again when the calibration is ready e To exit the menu press ESC After the calibr...

Page 105: ...me delay for each fault will then be reduced i e you might find some faults now instead of later The Sensitive fault detection mode turned on is indicated by the LED Routing equipment Fault tx activat...

Page 106: ...n backup duration etc The Service mode for COM loop is indicated by LED Fault Disablements General disablements and the symbol is flashing If the user stays in this menu window without doing any actio...

Page 107: ...by battery backup BATTERY Voltage The battery voltage at connector J4 4 5 Charging current The battery charging current for the selected control unit c i e Temperature The temperature detected by the...

Page 108: ...number and control unit number and press d Please wait No or very small current consumption 10 mA cannot be presented correctly precisely since the accu racy is 5 mA If you get No reply from control u...

Page 109: ...it length fault is the received number of bit length faults and bit length faults in relation to the pollings The number of Parity faults Number of bit faults No answer and Bit length faults shall nor...

Page 110: ...gade Panels General Control Panel A specific unit or all units connected to one c i e can be activated for address setting The units have to be in operation and in quiescent condition which means the...

Page 111: ...ess units 4611 4614 4645 to the Base station Unregister in order to unregister one or more wireless units 4611 4614 4645 from the Base station Install in order to change the communication from normall...

Page 112: ...d Domain Domain if programmed for the PC that was used for the SSD download EBLWin key The unique number for EBLWin key Convention Country specific functions default EBLWin settings and so on is set i...

Page 113: ...erviced but acknowledged faults Acknowledged Corrected serviced but not acknowledged faults Serviced a Log on to the c i e b Navigate to menu H6 c Press or to scroll in the list d To acknowledge a fau...

Page 114: ...ated routing equipment activated and so on See also section 5 4 INFORMATION PRIORITY ORDER on page 18 The Base station must be set back to the Normal state for the wireless detectors to function norma...

Page 115: ...are disabled In order to shorten the testing time any time delay for the detectors zones in test mode will be disabled i e fire alarm will be detected faster than normally In the tested alarm point t...

Page 116: ...oops are indicated by LED Fault Disablements General disablements the symbol is flashing and disconnected loops are listed in menu H4 U1 When you re connect a COM loop all the statistics shown in menu...

Page 117: ...l as soon as possible The first week average sensor value after acknowledge will be calculated within one hour then each week Sensors 4400 4401 set in advanced mode and 4402 always set in normal mode...

Page 118: ...rit the old sensor s value It is possible to clear the week average sensor value for each sensor individually via this menu The first week average sensor value after clearing will be calculated within...

Page 119: ...rol units can be selected When the test starts the alarm devices will sound continuously steady for approx 5 sec onds be silent for approx 25 seconds sound for approx 5 seconds and so on For the alarm...

Page 120: ...ut down can be performed from any control unit and any control unit can be selected A control unit without a front has to be shut down from another control unit By restart and power off the Fault tx o...

Page 121: ...might be empty which means the default settings will be used Or the stored data might be old and not valid 34 5 1 AFTER RESTART After a restart see chapter 25 RESTART on page 82 there will always be...

Page 122: ...ode alarm If a real fire alarm occurs the Test mode alarm will be automatically reset by the actual fire alarm A detector programmed for Quiet alarm will activate a Quiet test alarm instead of a fire...

Page 123: ...the control unit CU respectively Blank Synchronization failed for the control unit CU respectively a Log on to the c i e b Navigate to menu S7 c Write control unit number and press to select Yes Sync...

Page 124: ...tput will be reset only if the control expression is false If the control expression is true when you reset the output via menu H8 S8 the output will remain activat ed until the control expression is...

Page 125: ...ACTIVATED INTERLOCKING OUTPUTS INPUTS H9 C1 This menu is read only and or print available a Log on to the c i e b Navigate to menu C1 c Press or to scroll in the list d Press ESC to leave this menu In...

Page 126: ...s been false again Also a latched output will be deactivated If an interlocking output is activated via its control expression and with latching output selected in EBLWin the output must be deactivate...

Page 127: ...possible to get a print out The LED Fault Disablements General disablements is also indicating one or more disabled interlocking outputs a Log on to the c i e b Navigate to menu C3 c Write the area nu...

Page 128: ...be used to start a print out During printing the same soft key might change to Abort printing 37 1 HOW TO CHANGE PAPER IN THE PRINTER When the paper roll is almost empty a red line appears on one edge...

Page 129: ...n TLON Manager version 1 2 do Replace Update and Save In TLON Manager version 2 0 do Replace and Update Save is automatically done REPLACING BOTH A TLON CONNECTION BOARD 5090 AND ALSO THE MAIN BOARD A...

Page 130: ...echargeable Sealed Lead Acid batteries shall fulfil UL94V 0 The batteries are normally maintenance free but the producer s instructions shall always be followed The ambient temperature affects the bat...

Page 131: ...ventilation can cause a fire alarm Welding grinding cutting sawing drilling These kinds of jobs cause smoke CARPET WELDING Welding of plastic carpets causes a smoke that can be almost invisible but i...

Page 132: ...ing another type of detector can solve certain problems Bear also in mind that the coverage area can be different for differ ent types of detectors It is however not always the best action to change d...

Page 133: ...cts must absolutely not be stuck into the sensor detector Static electricity might destroy the detector Defective faulty discarded and replaced sensors detectors shall be taken care of as radioactive...

Page 134: ...TING INSTRUCTIONS V 3 0 0 DOCUMENT NUMBER MEW02760 DATE OF ISSUE 2022 03 07 REV DATE OF REVISION Panasonic Fire Security Europe AB Jungmansgatan 12 SE 211 11 Malm SE Tel 46 0 40 697 70 00 www panasoni...