Table 11: Modbus address list for flare.IQ Gen 1 legacy customers (analog inputs for flare control)
Register tag name
Register
address
Number of
registers
Description
Scaling
factor
PAIR_TC
62
1
Assist air pressure, iwg
*100
QN2_TC
70
1
Volumetric flow of nitrogen, scfh
*10
MW_LOW_CF
81
1
Low molecular weight correction factor
*100
MW_NORM_CF
82
1
Normal molecular weight correction factor
*100
MW_HIGH_CF
83
1
High molecular weight correction factor
*100
GC_UPDATE_RATE
90
1
Expected time between GC/MS updates, seconds
*1
MW_LOW
110
1
Low molecular weight to apply correction factor
*100
MW_NORM
111
1
Normal molecular weight to apply correction factor
*100
MW_HIGH
112
1
High molecular weight to apply correction factor
*100
QFUEL_MIN
130
1
Minimum fuel flow parameter, SCFH
*1
QFUEL_MAX
131
1
Maximum fuel flow parameter, SCFH
/10
FLARE_DIAM
140
1
Flare tip diameter, inches
*100
FLARE_METER_DIAM
141
1
Flare meter diameter, inches
*100
QSTEAM_MIN
150
1
Minimum steam flow parameter, PPH
*1
QSTEAM_MAX
151
1
Maximum steam flow parameter, PPH
/10
QAIR_LOW
160
1
Low air flow, CFM
/10
QAIR_MID
161
1
Mid air flow, CFM
/10
QAIR_HIGH
162
1
High air flow, CFM
/10
QAIR_MIN
170
1
Minimum air flow parameter, CFM
*1
QAIR_MAX
171
1
Maximum air flow parameter, CFM
/100
44
Summary of Contents for flare.IQ Generation 2
Page 1: ...flare IQ Generation 2 Operation and maintenance manual...
Page 2: ...2...
Page 3: ...flare IQ Generation 2 Operation and maintenance manual 910 350 rev A June 2020 3...
Page 4: ...no content intended for this page 4...
Page 38: ...Figure 30 System wiring diagram 38...
Page 48: ...48...