11
The user can switch between different parameters by turning the knob (4). By pres-
sing the knob you enter the mode of change of the selected parameter – the para-
meter will be backlit. You can change the value of the selected parameter by turning
the knob. To confirm the change press the knob again, and the controller will return
to the list of parameters. To leave the mode of change and restore the previous va-
lue of a parameter, press the MENU or ESC button. If the device is left either in the
changing or viewing the parameters mode for 60 seconds, removal of the modifica-
tion introduced recently and switching in the mode of displaying the device status will
occur automatically.
Table 2. User settings list.
L.p
Parameter
Min
Max
1.1
Fuel type.
1
4
1.2
Desired boiler temperature.
40°C
90°C
1.3
Boiler max. power.
60%
100%
1.4
Central heating pump operation mode .
WINTER SUMMER
1.5
Domestic water desired temperature.
30°C
60°C
1.6
Domestic water heating priority.
NO
YES
1.7
Domestic water tank bacterial flora liquidation program.
NO
YES
1.8
Measured domestic water temperature.
1.9
Measured return water temperature.
1.10 Temperature of the burner (PT–1000, CT–1/2).
1.11 1.12 Ignitor turn-off depending on the temperature.
200°C
500°C
1.13 Current furnace brightness (FD–1).
1.14 Ignitor turn-off depending on the illuminance value.
0
255
1.15 Burner running time.
1.16 Number of inflammation burner.
1.17 Boiler is turned on.
NO
YES
1.18 DHW heating is turned on.
NO
YES
1.19 Alarms cancellation.
1.20 Burner working mode. (CONTINUOUS, CYCLIC, CONTINUOUS PLUS,
MINIMUM POWER ).
1.21 SUMMER threshold temperature.
1°C
30°C
1.22 WINTER threshold temperature.
0°C
29°C
1.23 Increasing the temperature of the boiler.
NO
YES
1.24 Heating circuit 2.
NO
YES
1.1 Fuel type selection –
RK-2006SPGMS controller enables programming ignition
settings for four different fuel types. „Fuel type” parameter enables switching betwe-
en particular settings. Fan, auger and igniter operation are saved for the selected
fuel type. PELLET 1,2,3 and WOOD. When the WOOD fuel is set, you can burn the
wood in the pellet boiler – the controller operates at the wood fuel burning settings.
WOOD/PELLET – once the wood has been burned, the controller switches to pellet
burning and full service to the pellet boiler is provided.
CAUTION!
Fuel type may be changed, if the controller is in STOP mode only.