background image

14

CONTINUOUS PLUS

– the burner is continuously turned on (except from

emergencies)and ignites andheats up automatically even when the contacts of the

thermostat are opened (unlike the continuous mode, when contacts of the thermo-

stat should be closed to heat up the burner).

MINIMUM POWER

– mode similar to the usual mode of operaation with an excep-

tion that the burner works with MINIMUM power only, and it does not switch to mo-

dulated or maximum power.

1.21 SUMMER threshold temperature

– The transition temperature control in

SUMMER mode.

1.22 WINTER threshold temperature

– The transition temperature control in

WINTER mode.

1.23 Increasing the temperature of the boiler

– this parameter allows you to

adjust the characteristics of a weather cycle 1 to cycle 2.

1.24 Heating circuit 2

– This parameter enables the activation and operation mode

selection circuit 2.

YES

– 2 circuit activates.

AUTO

– 2 circuit is switched on after passing the controller in operation mode

WINTER.

7. Setting the parameters – service mode.

Service parameters are divided into groups. For each group are assigned service

parameters possible to change. Entry into service mode after press and hold for

about 3 seconds the MENU button. regulator displays a list of service parameters

possible to edit and change.

Viewing the list of parameters is possible by turning the multifunction knob - possible

to edit the parameter is highlighted. After selecting the desired parameter press the

OK button (knob), and enter the subgroups of a given parameter. Select the

parameter you want to change and press the knob - a parameter is highlighted.

Turning the knob set the desired value and then press the knob. Giving up mode

changes and restore the previous value of the parameter by pressing the STOP

button or ESC. If the unit is left in a mode change or view the parameters for 60

seconds, the controller will automatically withdraw the recently introduced

modification and switch to display the status of the device. A list of all service

parameters presented in the table. The table columns contain the following order:

group number, name of the parameter and the value of the minimum and maximum

possible settings.

Summary of Contents for RK-2006SPGMS

Page 1: ...OPERATION MANUAL RK 2006SPGMS Pellet fuel burner fitted boiler temperature controller Version 8B28 version of the adapter MZK MZM2...

Page 2: ......

Page 3: ...er The temperature sensor should be placed in metering locations that shall be dry Figure 2 presents the electrical connection diagram CAUTION Before plugging in the controller first check if the wiri...

Page 4: ...of the device is to set the preset boiler temperature In this hands U need to turn the boiler thermostat knob 4 to set the correct value and confirm it with the OK button or press the knob CAUTION If...

Page 5: ...ty indicator the higher the capacity the brighter the flame 10 Cleaning device work indicator 11 Stoker work indicator 12 Feeder temperature 13 The operation indicator summer mode 14 The temperature c...

Page 6: ...water pumps operation but automatic ignition does not follow AUGER EXTINCT EMERGENCY SHUT DOWN Fuel ignition in auger channel The controller empties ignited fuel from the auger channel until temperatu...

Page 7: ...feeding rate is adjusted by the technician Pressing STOP button exceeding time limit for cleaning thermostat contacts opening or if water temperature in domestic water tank is obtained during operati...

Page 8: ...uence Afterburning EXTINCTION CLEANING Automatic burner cleaning occurs after time set limit by programmer In this mode controller starts cleaning system for preset time After this procedure controlle...

Page 9: ...sensor Activation of the alarm will result in fan and auger turning off and switching the controller into STAND BY mode CAUTION This alarm does not result in engagement of inner sound system and does...

Page 10: ...Damage to the outside temperature sensor In the event of damage to the external temperature sensor controller causes alarm the minimum temperature is maintained in the circuits dependent the outside t...

Page 11: ...rature 1 9 Measured return water temperature 1 10 Temperature of the burner PT 1000 CT 1 2 1 11 1 12 Ignitor turn off depending on the temperature 200 C 500 C 1 13 Current furnace brightness FD 1 1 14...

Page 12: ...hot water without priority option central heating and domestic water pumps operation follow at the same timee 1 7 Bacterial flora liquidation in domestic water tank the controller enables manual activ...

Page 13: ...n burner work Parameters described below refer to counters that accumulate information on opera tion of the burner since its first start It is not possible to cancel counter readings 1 15 Burner work...

Page 14: ...arameters service mode Service parameters are divided into groups For each group are assigned service parameters possible to change Entry into service mode after press and hold for about 3 seconds the...

Page 15: ...uel feed 0s 250s F 4 3 Fuel feed cycle 1s 250s F 4 4 Fuel feed during ignition 0 100 F 4 5 Fuel feed for max burner power 1 100 F 4 6 Fuel feed for min burner power 1 100 F 4 7 Stoker work mode see de...

Page 16: ...Thermostat 9 1 Boiler minimum temperature 30 C 69 C F 9 2 Boiler maximum temperatur 70 C 90 C F 9 3 Boiler upper hysteresis 1 C 20 C F 9 4 Boiler power switching hysteresis 1 C 9 C F 9 5 Boiler prote...

Page 17: ...le to test various output devices This feature is available in service mode only if the adju stment process is stopped ie The regulator before entering the service mode was in STOP mode Selecting outp...

Page 18: ...the controller offers the function of scavenge air purging which simply includes periodical switching on of the fan during burner operation for the purpose of removal of accumulated gases 3 11 Fan sca...

Page 19: ...e lighter In this case Initial Fuel Dose set ting be shall be programmed as the value over 0s 4 5 Fuel feed for max burner power this parameter specifies fuel dose fed to the burner during operation w...

Page 20: ...selected in Auger ignition test setting and contacts of X input shall be closed 4 13 Auger ignition temperature this parameter specifies auger temperature when the controller activates auger ignition...

Page 21: ...time after igniter and fan are switched on the controller tests temperature increase or brightness in the selected location of the burner If flame is not detected within the time programmed in this pa...

Page 22: ...attached to the time set in parameter Cleaning mechanism work time After turning off the regulator output deducts the time set in parameter Cleaning mecha nism retraction time and the time set in par...

Page 23: ...e is tur ned on accordingly less often depending on the SECOND MECHANISM K DIVISOR parameter If K is 2 the bottom drawer is turned on at every second move of the top drawer AUTO ASH REMOVAL In other c...

Page 24: ...ired number of shut downs Setting the parameter to 0h control the minimum time off work without cleaning 6 9 The maximum working time without cleaning this parameter is available on ly when the cleani...

Page 25: ...domestic water path handling Election of MIXING PUMP setting will switch domestic water in the circuit purposed for control of the mixing pump In this case return water temperature sensor shall be co...

Page 26: ...burner due to excee ding the hysteresis top of the boiler This parameter specifies how long is needed to stabilize the system after the hot water tank with priority enabled During the stabili zation c...

Page 27: ...parameter specifies hysteresis parameter of boiler limit temperatures switching off 9 6 Boiler overheating temperature this parameter specifies boiler water temperature when the controller switches of...

Page 28: ...ate adaptive algorithm preset boiler temperature Value should be selected empirically according to the characteristics of the controlled object If you are working adaptive algorithm and frequently cha...

Page 29: ...no parity bits 2 bits of silence default setting 10 5 MODBUS access level defines to what extent the configuration of parameters is available to the ModBus protocol NONE no parameters are provided by...

Page 30: ...ump AUTO Continuous pump operation 13 3 Weather control This function allows you to attach a weather control 13 4 Temperature set point circuit the temperature is maintained behind the mixing valve 13...

Page 31: ...d ensure the system as well uses the main circuit as the central heating circula tion when the 2 circuit operates 13 14 Use the main thermostat when the parameter is set to YES the standard boiler the...

Page 32: ...e depends mainly on the outside temperature and thermal properties of a building The controller enables the user to set the adequate inclination and shift of the weather charcteristics The relations b...

Page 33: ...ther characteristics will be changed 8 Controller disassembly If controller disassembly is necessary follow the following procedure Disconnect the boiler and controller from power supply Remove the co...

Page 34: ...34 Figure RK 2006SPGMS Controller connection diagram...

Page 35: ...treated as household waste The appliance shall be handed over to the applicable collection point for used up electrical and electronic equipment for recycling purpose Ultimate disposal of the applianc...

Page 36: ...Manufacturer P W KEY 11 200 Bartoszyce ul Bohater w Warszawy 67 tel 89 763 50 50 fax 89 763 50 51 www pwkey pl e mail pwkey onet pl...

Reviews: