4.x Fuel auger operation parameters.
4.1 Auger filling time
– this parameter specifies time required for refilling the main
auger with fuel.
4.2 Initial fuel feed
– this parameter specifies time, when fuel will be fed before
igniter start. Selection of „0s” setting will switch off initial fuel dose feeding. In this ca-
se „Fuel dose during ignition” setting shall be programmed as the value over „0%”.
4.3 Fuel feed cycle
– auger operation cycle includes fuel feeding and feeding pau-
se. This parameter specifies the time of the whole cycle. The desired value specifies
all burner work modes which require fuel feeding (ignition, maximum and
minimum power).
4.4 Fuel feed during ignition
– this parameter specifies fuel dose that is fed to the
burner during lighter operation. The programmed setting specifies feeding time in
percent in relation to the time of whole work cycle. Selection of „0s” setting will
switch fuel feeding during operation of the lighter. In this case „Initial Fuel Dose” set-
ting be shall be programmed as the value over „0s”.
4.5 Fuel feed for max. burner power
– this parameter specifies fuel dose fed to the
burner during operation with maximum power. The programmed setting specifies fe-
eding time in percent in relation to the time of whole work cycle.
4.6 Fuel feed for min. burner power
– this parameter specifies fuel dose fed to the
burner during operation with minimum power. The programmed setting specifies
feeding time in percent in relation to the time of whole work cycle
4.7 Stoker work mode
– This parameter defines the operation of the internal tray
(stoker):
OFF
– the burner without the stoker.
CYCL
– stoker is switched on periodically, regardless of the auger. Work and pause
time of the stoker is determined with particular settings.
AUTO
– operation mode when the stoke is switched on along with the auger and is
switched off with a delay defined with „Stoker extra work time” setting.
4.8 Stoker work time
– this parameter specifies operation time of the stoker in who-
le work cycle. This setting is unavailable if the stoker is switched off or in automatic
mode.