P.W. KEY RK-2006SPGMS Manual Download Page 27

27

the lowest temperature setting of the boiler that can be programmed with

thermostat’s knob.

9.2 Maximum boiler temperature –

this parameter specifies boiler max. program-

med temperature setting which can be programmed with thermostat’s knob. It is also

boiler temperature when central heating pump is engaged to provide protection for

the boiler against overheating.

9.3 Boiler upper hysteresis

– if the controller works in burner minimum power

mode, and boiler temperature increase follows by this programmed setting, the

controller will start burner extinction(shut down).

9.4 Burner power switching hysteresis –

when the programmed boiler water

temperature is obtained the controller is switched to minimum power work mode.

This parameter specifies required water temperature drop so that maximum power

work mode was activated. After switching to maximum power the fuel and air feeding

dose is determined according to burner power modulation.

9.5 Boiler protection hysteresis

– the controller provides for boiler minimum and

maximum temperature by providing control over operation of central heating and do-

mestic water pumps. This parameter specifies hysteresis parameter of boiler limit

temperatures switching off.

9.6 Boiler overheating temperature

– this parameter specifies boiler water

temperature when the controller switches off control and activates boiler overheating

alarm.

9.7 Burner power modulation

– when modulation is switched on it will results in

gradual reduction of fan speed and fuel dose to obtain boiler water temperature

corresponding to the programmed setting.

9.8 Burner power modulation factor

– this parameter specifies degree setting

when the controller will reduce burner power before boiler water temperature is

obtained according to the programmed setting. Burner power is reduced by gradual

reduction of fed fuel dose and fan speed reduction. This parameter is unavailable, if

burner modulation power is off.

The room thermostat.

RK-2006SPGMS was equipped with an input for connecting any room thermostat

with contact output. Contacts of the thermostat is signaled by the appearance of the

thermometer symbol in the index of the thermostat.

CAUTION!

The entrance of the room thermostat is active only during WINTER.

Lights up when the input state is independent of the mode setting.

9.9 Mode of operation of the room thermostat

– this parameter determines the

impact of the entry of the room thermostat to the operation of the controller:

Summary of Contents for RK-2006SPGMS

Page 1: ...OPERATION MANUAL RK 2006SPGMS Pellet fuel burner fitted boiler temperature controller Version 8B28 version of the adapter MZK MZM2...

Page 2: ......

Page 3: ...er The temperature sensor should be placed in metering locations that shall be dry Figure 2 presents the electrical connection diagram CAUTION Before plugging in the controller first check if the wiri...

Page 4: ...of the device is to set the preset boiler temperature In this hands U need to turn the boiler thermostat knob 4 to set the correct value and confirm it with the OK button or press the knob CAUTION If...

Page 5: ...ty indicator the higher the capacity the brighter the flame 10 Cleaning device work indicator 11 Stoker work indicator 12 Feeder temperature 13 The operation indicator summer mode 14 The temperature c...

Page 6: ...water pumps operation but automatic ignition does not follow AUGER EXTINCT EMERGENCY SHUT DOWN Fuel ignition in auger channel The controller empties ignited fuel from the auger channel until temperatu...

Page 7: ...feeding rate is adjusted by the technician Pressing STOP button exceeding time limit for cleaning thermostat contacts opening or if water temperature in domestic water tank is obtained during operati...

Page 8: ...uence Afterburning EXTINCTION CLEANING Automatic burner cleaning occurs after time set limit by programmer In this mode controller starts cleaning system for preset time After this procedure controlle...

Page 9: ...sensor Activation of the alarm will result in fan and auger turning off and switching the controller into STAND BY mode CAUTION This alarm does not result in engagement of inner sound system and does...

Page 10: ...Damage to the outside temperature sensor In the event of damage to the external temperature sensor controller causes alarm the minimum temperature is maintained in the circuits dependent the outside t...

Page 11: ...rature 1 9 Measured return water temperature 1 10 Temperature of the burner PT 1000 CT 1 2 1 11 1 12 Ignitor turn off depending on the temperature 200 C 500 C 1 13 Current furnace brightness FD 1 1 14...

Page 12: ...hot water without priority option central heating and domestic water pumps operation follow at the same timee 1 7 Bacterial flora liquidation in domestic water tank the controller enables manual activ...

Page 13: ...n burner work Parameters described below refer to counters that accumulate information on opera tion of the burner since its first start It is not possible to cancel counter readings 1 15 Burner work...

Page 14: ...arameters service mode Service parameters are divided into groups For each group are assigned service parameters possible to change Entry into service mode after press and hold for about 3 seconds the...

Page 15: ...uel feed 0s 250s F 4 3 Fuel feed cycle 1s 250s F 4 4 Fuel feed during ignition 0 100 F 4 5 Fuel feed for max burner power 1 100 F 4 6 Fuel feed for min burner power 1 100 F 4 7 Stoker work mode see de...

Page 16: ...Thermostat 9 1 Boiler minimum temperature 30 C 69 C F 9 2 Boiler maximum temperatur 70 C 90 C F 9 3 Boiler upper hysteresis 1 C 20 C F 9 4 Boiler power switching hysteresis 1 C 9 C F 9 5 Boiler prote...

Page 17: ...le to test various output devices This feature is available in service mode only if the adju stment process is stopped ie The regulator before entering the service mode was in STOP mode Selecting outp...

Page 18: ...the controller offers the function of scavenge air purging which simply includes periodical switching on of the fan during burner operation for the purpose of removal of accumulated gases 3 11 Fan sca...

Page 19: ...e lighter In this case Initial Fuel Dose set ting be shall be programmed as the value over 0s 4 5 Fuel feed for max burner power this parameter specifies fuel dose fed to the burner during operation w...

Page 20: ...selected in Auger ignition test setting and contacts of X input shall be closed 4 13 Auger ignition temperature this parameter specifies auger temperature when the controller activates auger ignition...

Page 21: ...time after igniter and fan are switched on the controller tests temperature increase or brightness in the selected location of the burner If flame is not detected within the time programmed in this pa...

Page 22: ...attached to the time set in parameter Cleaning mechanism work time After turning off the regulator output deducts the time set in parameter Cleaning mecha nism retraction time and the time set in par...

Page 23: ...e is tur ned on accordingly less often depending on the SECOND MECHANISM K DIVISOR parameter If K is 2 the bottom drawer is turned on at every second move of the top drawer AUTO ASH REMOVAL In other c...

Page 24: ...ired number of shut downs Setting the parameter to 0h control the minimum time off work without cleaning 6 9 The maximum working time without cleaning this parameter is available on ly when the cleani...

Page 25: ...domestic water path handling Election of MIXING PUMP setting will switch domestic water in the circuit purposed for control of the mixing pump In this case return water temperature sensor shall be co...

Page 26: ...burner due to excee ding the hysteresis top of the boiler This parameter specifies how long is needed to stabilize the system after the hot water tank with priority enabled During the stabili zation c...

Page 27: ...parameter specifies hysteresis parameter of boiler limit temperatures switching off 9 6 Boiler overheating temperature this parameter specifies boiler water temperature when the controller switches of...

Page 28: ...ate adaptive algorithm preset boiler temperature Value should be selected empirically according to the characteristics of the controlled object If you are working adaptive algorithm and frequently cha...

Page 29: ...no parity bits 2 bits of silence default setting 10 5 MODBUS access level defines to what extent the configuration of parameters is available to the ModBus protocol NONE no parameters are provided by...

Page 30: ...ump AUTO Continuous pump operation 13 3 Weather control This function allows you to attach a weather control 13 4 Temperature set point circuit the temperature is maintained behind the mixing valve 13...

Page 31: ...d ensure the system as well uses the main circuit as the central heating circula tion when the 2 circuit operates 13 14 Use the main thermostat when the parameter is set to YES the standard boiler the...

Page 32: ...e depends mainly on the outside temperature and thermal properties of a building The controller enables the user to set the adequate inclination and shift of the weather charcteristics The relations b...

Page 33: ...ther characteristics will be changed 8 Controller disassembly If controller disassembly is necessary follow the following procedure Disconnect the boiler and controller from power supply Remove the co...

Page 34: ...34 Figure RK 2006SPGMS Controller connection diagram...

Page 35: ...treated as household waste The appliance shall be handed over to the applicable collection point for used up electrical and electronic equipment for recycling purpose Ultimate disposal of the applianc...

Page 36: ...Manufacturer P W KEY 11 200 Bartoszyce ul Bohater w Warszawy 67 tel 89 763 50 50 fax 89 763 50 51 www pwkey pl e mail pwkey onet pl...