![OutBack Power EnergyCell 1100RE Installation Manual And Owner'S Manual Download Page 60](http://html1.mh-extra.com/html/outback-power/energycell-1100re/energycell-1100re_installation-manual-and-owners-manual_1660771060.webp)
Publication No. US-VR-OM-002
March 2008
www.enersys.com
21
8.3.1 Equalizing Charge Method
Constant voltage charging is the method for giving an equalizing charge. To perform an
equalizing charge, follow the procedure below:
1.
Determine the maximum voltage that may be applied to the system equipment.
2.
Divide this voltage by the number of cells connected in a series.
This is the MAXIMUM VOLTS PER CELL to be used for the equalizing charge.
This number should NOT exceed 2.35 VOLTS PER CELL average.
3.
Use Table 8.2 to determine the equalize charge time.
The times listed are the number of hours to charge the battery system AFTER the charge
current has been stabilized for three hours.
Stabilization occurs when the current level remains constant for three hours.
TABLE 8.2
CELL
VOLTS
TIME (hours)
AFTER CURRENT STABILIZATION
(3 hours without change)
AT AMBIENT TEMPERATURES FROM
70-90˚F (21-32˚C)
TIME (hours)
AFTER CURRENT STABILIZATION
(3 hours without change)
AT AMBIENT TEMPERATURES FROM
55-69˚F (13-20˚C)
2.32
24
48
2.35
12
24
During charge, if the cell/battery temperature exceeds 105˚F
(40˚C) stop the charge immediately and allow the temperature
to decrease below 90˚F (32˚C). Failure to follow this warning
may result in severe overcharge and damage to the cell/battery.
CAUTION
Summary of Contents for EnergyCell 1100RE
Page 1: ...EnergyCell RE High Capacity Battery Installation Guide and Owner s Manual...
Page 4: ......
Page 28: ...Page 18 Publication No US DDm IM 003 www enersysinc com November 2003 NOTES...
Page 29: ......
Page 66: ...BATTERY MAINTENANCE REPORT DDm DDS DDV DGX mSeries and SC...
Page 67: ...BATTERY MAINTENANCE REPORT DDm DDS DDV DGX mSeries and SC...
Page 69: ...30 www enersys com Publication No US VR OM 002 March 2008 NOTES...