EnergyCell RE High Capacity Specifications
Models
:
800RE
1100RE
1300RE
1600RE
2000RE
2200RE
2700RE
EnerSys Part Number
DDm85-15
DDm85-21
DDm100-21
DDm100-25
DDm125-25
DDm100-33
DDm125-33
Nominal Voltage Per Cell
2V
2V
2V
2V
2V
2V
2V
Capacity 20Hr Rate
(1.75VPC)
672
960
1148
1378
1716
1836
2288
Capacity 100Hr Rate
(1.75VPC)
810
1150
1340
1600
2070
2140
2770
Watts Per Cell 15min Rate
(1.67VPC)
1230
1757
1995
2394
3071
3192
4094
Cycle Life 50% DOD
(25°C)
1800 cycles
1800 cycles
1800 cycles
1800 cycles
1800 cycles
1800 cycles
1800 cycles
Optimal Operating Temperature Range
23 to 26°C
23 to 26°C
23 to 26°C
23 to 26°C
23 to 26°C
23 to 26°C
23 to 26°C
OCV Per Cell Limit
*
2.05
2.05
2.05
2.05
2.05
2.05
2.05
Initial Charge Voltage Per Cell
**
2.27
2.27
2.27
2.27
2.27
2.27
2.27
Float Voltage Per Cell
(25°C)
2.25
2.25
2.25
2.25
2.25
2.25
2.25
Float Voltage Per Cell
(35°C)
2.21
2.21
2.21
2.21
2.21
2.21
2.21
Equalize Voltage Per Cell
(21 to 32°C)
2.32
2.32
2.32
2.32
2.32
2.32
2.32
Maximum Charge Current
(A)
148.75
212.5
250
300
375
400
500
Shelf Life
(25°C)
6 months
6 months
6 months
6 months
6 months
6 months
6 months
Short Circuit Current
(A)
4728
6748
7722
9267
12411
12337
16548
Internal Resistance
(micro Ω)
441
309
270
225
167
169
126
Terminal Torque
(Intercell Connects)
88 in-lbs
Hardware Specification
(Intercell Connects)
M8 bolt, lock and flat washer
Weight Per Cell
(lbs)
114.3
162.3
188.3
222.3
272.3
290.3
358.3
Dimensions Per Cell L x W x H
(in)
21.8 x 11.9 x 6.5
21.8 x 8.4 x 6.5
24.5 x 8.4 x 6.5
24.5 x 9.9 x 6.5
23.5 x 9.9 x 8.9
24.5 x 12.9 x 6.5
23.5 x 12.9 x 8.9
Ah Capacity to 1.75VPC @ 25°C
Models
:
800RE
1100RE
1300RE
1600RE
2000RE
2200RE
2700RE
1 hour
347
495
575
690
886
920
1182
2 hours
440
631
738
884
1138
1180
1518
3 hours
492
702
822
987
1260
1317
1680
4 hours
528
752
876
1052
1332
1404
1776
5 hours
555
790
920
1105
1390
1470
1850
6 hours
576
822
954
1146
1440
1524
1914
8 hours
600
864
1008
1208
1512
1616
2016
10 hours
610
870
1040
1250
1550
1660
2060
12 hours
624
888
1068
1284
1584
1704
2112
20 hours
672
960
1148
1378
1716
1836
2288
24 hours
676
984
1176
1416
1776
1872
2352
100 hours
810
1150
1340
1600
2070
2140
2770
Purpose
This document provides the EnergyCell RE High Capacity Installation Guide and Operation Manual.
Scope
This document applies to all models of the EnergyCell RE High Capacity series. The reference table below shows the Outback part
number cross referenced with the manufacturer part number. When using this document for installation and service operations,
please refer to the manufacturer part number when referencing critical information.
Should you have ANY questions concerning how to perform the required maintenance or installation please contact Outback
Power at the office number listed below and ask for Outback Power Tech Support.
Summary of Contents for EnergyCell 1100RE
Page 1: ...EnergyCell RE High Capacity Battery Installation Guide and Owner s Manual...
Page 4: ......
Page 28: ...Page 18 Publication No US DDm IM 003 www enersysinc com November 2003 NOTES...
Page 29: ......
Page 66: ...BATTERY MAINTENANCE REPORT DDm DDS DDV DGX mSeries and SC...
Page 67: ...BATTERY MAINTENANCE REPORT DDm DDS DDV DGX mSeries and SC...
Page 69: ...30 www enersys com Publication No US VR OM 002 March 2008 NOTES...