Page 14
Publication No. US-DDm-IM-003
www.enersysinc.com
November
2003
Inter-Cell Connectors
The connections are made by bolting the
supplied lead-plated copper inter-cell and inter-
module connectors to the cell posts of opposite
polarity on adjacent cells. See
ASSEMBLY
DRAWING
for details.
1. Clean the contact surface of the inter-cell
connector using a stiff-bristle nonmetallic
brush/pad. Be careful not to remove the
lead plating with excessive brushing.
2. Apply a light coat of heated NO-OX-ID
grease to the contact surface of the inter-cell
connector and terminal post with a small
paintbrush.
3. Bolt all inter-cell connectors according to the
ASSEMBLY DRAWING.
Assemble as the
example shown in Figure 25 and below list:
•
Bolt (M8)
•
Lock Washer
•
Flat Washer
•
Inter-cell Connector
•
Battery Post
4. Secure all connections finger-tight to allow
for some adjustment of position.
5. After all connections are completed, torque
to 88 in-lbs.
6. Apply a light coat of heated NO-OX-ID
grease to the bolted connection with a small
paintbrush.
INSTALL INTERCELL
CONNECTORS
FIGURE 25
Stamped flat washers may have one
sharp edge. Install the washer with the
sharp edge away from the lead-plated
copper inter-cell connector to avoid
damaging the lead plating.
NOTE:
Inter-cell connections vary in length
depending on the type of connection (cell-to-
cell, module-to-module, etc.) and/or stack
configuration.
Summary of Contents for EnergyCell 1100RE
Page 1: ...EnergyCell RE High Capacity Battery Installation Guide and Owner s Manual...
Page 4: ......
Page 28: ...Page 18 Publication No US DDm IM 003 www enersysinc com November 2003 NOTES...
Page 29: ......
Page 66: ...BATTERY MAINTENANCE REPORT DDm DDS DDV DGX mSeries and SC...
Page 67: ...BATTERY MAINTENANCE REPORT DDm DDS DDV DGX mSeries and SC...
Page 69: ...30 www enersys com Publication No US VR OM 002 March 2008 NOTES...