4.1
General
Batteries should be unpacked, installed and charged as soon as possible after receipt.
However, if this is impractical, follow the instructions below for storing the battery before
installation.
4.2
Storage Location
1.
Store batteries indoors in a clean, dry and cool location. Storage at higher
temperatures will result in accelerated rates of self-discharge and possible
deterioration of battery performance and life.
2.
Do
NOT
stack pallets.
DAMAGE MAY OCCUR AND THE WARRANTY MAY BE VOIDED.
3.
The maximum storage time from shipment to initial charge is six months for batteries
stored at ambient temperatures no warmer than 77˚F (25˚C). For storage temperatures
greater than 77˚F (25˚C), the battery must be recharged one (1) month sooner for every
5˚F (3˚C) increase above 77˚F (25˚C). See Table 4.1.
4.0 BATTERY STORAGE BEFORE INSTALLATION
Publication No. US-VR-OM-002
March 2008
www.enersys.com
9
TABLE 4.1
STORAGE TEMPERATURE
STORAGE TIME
32˚F (0˚C) to 50˚F (10˚C)
9 months
51˚F (11˚C) to 77˚F (25˚C)
6 months
78˚F (26˚C) to 92˚F (33˚C)
3 months
If storage time exceeds the storage time recommended in Table 4.1, give the battery a
freshening charge before the end of the recommended storage interval. See Section 7 for
charging information.
PowerSafe™ VRLA mSeries, DDm, DDS and DDV batteries must be charged in the horizontal
position. Charging in the vertical position could void the warranty.
4.
Repeat the
freshening charge
for each additional storage interval until the battery is installed.
Storage at higher temperatures will result in accelerated rates of self-discharge and possible
deterioration of battery performance and life. Storage times exceeding the above may result
in plate sulfation, which may adversely affect electrical performance and expected life.
5.
Maximum total storage time prior to installation is two (2) years from date of shipment
from the factory to the customer.
Freshening charges
are required before the end of the
storage time period, or more frequently, as noted in Table 4.1.
6. FAILURE TO CHARGE AS NOTED VOIDS THE BATTERY'S WARRANTY.
Summary of Contents for EnergyCell 1100RE
Page 1: ...EnergyCell RE High Capacity Battery Installation Guide and Owner s Manual...
Page 4: ......
Page 28: ...Page 18 Publication No US DDm IM 003 www enersysinc com November 2003 NOTES...
Page 29: ......
Page 66: ...BATTERY MAINTENANCE REPORT DDm DDS DDV DGX mSeries and SC...
Page 67: ...BATTERY MAINTENANCE REPORT DDm DDS DDV DGX mSeries and SC...
Page 69: ...30 www enersys com Publication No US VR OM 002 March 2008 NOTES...