19
4
Detachable strip connectors (power supply, battery
backup, RS-485 bus connections, outputs)
Connector markings:
91 24
Vac power supply
GND
92
12
Vdc backup voltage input
BG
RS-485 bus isolated ground
A1 and B1 RS-485 bus connection
A2 and B2 RS-485 bus connection
42 and 43 24 Vac output (Triac or continuous 24 Vac)
61 0…10
V
output
GND
44 and 45 24 Vac output (Triac or continuous 24 Vac)
62 0…10
V
output
GND
5
Detachable strip connectors
(Change-over contact relays max 230 Vac, 6 A)
Connector markings:
71 Relay
1
NO
72 Relay
1
C
73 Relay
1
NC
74 Relay
2
NO
75 Relay
2
C
76 Relay
2
NC
6
Detachable strip connectors
(relays with normally open contact max 230 Vac, 6 A)
Connector markings:
77 Relay
3
NO
78 Relay
3
C
79 Relay
4
NO
80 Relay
4
C
81 Relay
5
NO
82 Relay
5
C
83 Relay
6
NO
84 Relay
6
C
3
Detachable strip connector
(operation voltage and outputs)
Connector markings:
41 24
Vac operating voltage output
GND
63 0…10
V
output
41 24
Vac
operating
voltage
output
GND
64 0…10
V
output
41 24
Vac
operating
voltage
output
GND
65 0…10
V
output
41 24
Vac
operating
voltage
output
GND
66 0…10
V
output
41 24
Vac
operating
voltage
output
GND
93 15
Vdc
operating
voltage
output
GND
Detachable strip connectors
(universal measurement, digital and pulse counter inputs)
Connector markings:
1…12 Universal
input
13…16
Universal
input,
pulse
counter
input
21...22
Digital
input,
pulse
counter
input
2
Detachable strip connectors
(measurements’ ground)
Connector labels
… Measurements’ ground (16pcs)
1
71 72 73
74 75 76
77 78
79 80
81 82
83 84
1 2 3 4 5 6 7 8 9
10 11 12 13 14 15 16 21 22
41
41
41
41
41
63
64
65
66
93
4
5
5
6
6
6
6
3
2
2
1
1
91
92 BG A1 B1 A2 B2 42 43 61
44 45 62
Ouflex includes 34 I/O-points, and also versatile data transfer and field bus connections. In additi-
on, the device contains 24 Vac and 15 Vdc outputs. Display unit is detachable, and can be relocated.
It is possible to increase the number of I/O-points with external I/O-modules via bus connections.