EH-105
MEASUREMENTS
EH-105
OPERATING INSTRUCTIONS:
Measured value outside of sensor' range:
Indication of sensor defect:
Each sensor has its own typical range. (E.g., outdoor sensor -50...+50 °C). If the
sensor's measured value is outside of this range, a or + character will appear on the
”Measurements” display at the sensor's measured value to indicate whether the value
is above or below the range.
If there is a sensor defect the controller gives an alarm (see p. 18) and ”err” will appear
in place of the measured value.
The controller can be connected to 18 different measurement data at the same
time (6 NTC measurements, 5 transmitter measurements and 7 digital outputs) If
a measurement is reserved for alarms or for a free temperature measurement, it
can be labeled accordingly. Measurements can be taken into use or removed
from use in the maintenance mode (see p. 42-43).
Measurements °C
Room temp. 21.5
ExhausTemp 21.5
SupplyTemp 19.5
Select
Measurements
AHU oper.contr.
Settings
Supply air info
AHU output info
Connection info
ControlOperMode
Clock functions
Alarms
Language/kieli
Type info
Initializ.modem
Mainten.mode
L1
Ulkol. °C
Menovesi °C
Valinta
Automaattiohj
L1
Ulkol. °C
Menovesi °C
Valinta
Automaattiohj
AHU 1/1 Autom.
Room temp.21.2
SupplyTemp20.4
Selection
°C
°C
Also, the state of the voltage controlled (0…10V or 2…10V) actuator can be seen on the
measurements display. Measurement info can also be read through the bus interface or
a GSM.
Only the measurements connected to the controller appear on the display.
Text on the display:
Measurement information:
NTC measurements (strip connectors 1- 6)
Setting range:
Outdoor temp
SupplyTemp
Supp.TempB
Room temp
ExhausTemp
Room tempB
Rad.Ret.Wat
Exh.aft.HRU
SuppAfterHRU
RemoteSetPot
FreeMeasurem
-50 ... + 50°C
-30 ... +100°C
-30 ... +100°C
-30 ... +100°C
-30 ... +100°C
-30 ... +100°C
-30 ... +100°C
-30 ... +100°C
-30 ... +100°C
,
Transmitter measurements (strip connectors 7 - 11) The setting range is set in the maintenance mode
SF press.
EF press.
SF fan PDE
EF fan PDE
CO2cont.
Rh/pot
SF flow
EF flow
SFfilt.PDE
EF filt.PDE
HRU PD
Room temp
ExhausTemp
0 ... 999 Pa
0 ... 999 Pa
0...5000Pa
0...5000Pa
0 ... 2000 ppm
0 ... 100 %
0.0 ... 10.0 m/s
0.0 ... 10.0 m/s
0 ... 999 Pa
0 ... 999 Pa
0 ... 999 Pa
-20 ... +100
-20 ... +100
°C
°C
-30 ... +100°C
-5 ... +
4°C
Press the
button to enter the
measurements mode directly from the basic
display (In addition to the normal menu path)
+
Hint!
Hint!
Press the
button to browse measurements
Outdoor temperature (connect to measurement 1)
Supply air temperature after the fans
Supply air temperature before the cooling cell
Room temperature
Exhaust air temperature
Room temperature sensor 2 temperature (for computing the average)
Return water temperature
Exhaust air temperature after the HRU
Supply air temperature after the HRU
The remote setting potentiometer makes changes to the main setting in
supply controlled units or room controlled units.
Free temperature measurement, which can be labeled using the
text editor
Supply air pressure, pressure transmitter
Exhaust air pressure, pressure transmitter
Pressure difference over the supply fan or air flow volume measuring ring
Pressure difference over the exhaust fan or air flow volume measuring ring
CO2 content, carbon dioxide content transmitter
Room temperature humidity or remote setting trans.data ( transm.0...10V)
Supply air flow, flow transmitter
Exhaust air flow, flow transmitter
Pressure difference meas. over the supply air filter, pressure transmitter
Pressure difference meas. over the exhaust air filter, pressure transmitter
Pressure difference measurement over the HRU, pressure transmitter
Room temperature
Exhaust air temperature