Select
Mainten.mode
ON/OFF inputs
EH-105 has seven digital inputs that can receive contact information about AH
unit operation. (e.g., information about what state the AH unit is in when it is
running or On/Off alarm information). Contact information can also be connected
to NTC and transmitter measurement channels that have not been connected;
they are taken into use for this purpose here.
The symbol indicates which control the contact information is connected to.
C
+
AHU fan
Heating
Name change
GenAlarmOpen
Give new name
AHU output drop
from maximum
Enabled
Disabled
AH start after
alarm is deactiv
No acknowledg.
After acknowl.
The AH unit starts up 5 min. after the alarm has
disappeared without it being separately acknowledged.
Attention! Make sure that the pipe work is short enough so
it has time to warm up after a 5 minute delay and there is no
freezing risk, See p. 47.
You can label a general alarm. Directions for
using the text editor are outlined on page 6.
Note! The factory setting for the Emerg.Stop-
information is AH start after acknowledgement.
-
-
-
-
21
22
23
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
ON/OFF inputs:
F 1/1 run
E
1/1PowerSw
1/2PowerSw
AUTO Switch
Emerg.Stop
S
SF 1/2 run
EF 1/1 run
EF 1/2 run
SF fConvOver
EF fConvOver
SF fan PDS
EF fan PDS
Pumprun
Pump run
Pump run
SF 1/1TRela
SF 1/2TRela
F 1/1TRela
EF 1/2TRela
Pump T Rela
Pump T Rela
Pump T Rela
FrostPDS1/1
FrostPDS
FrostPDS1/2
SF filt.PDS
EF filt.PDS
Smoke alarm
Temperat. 2
ElHeatOverh
Water press
Glyc.press
Rotat.Alarm
ElHeatEmrgS
ElHeatPerm.
Mainten.SOP
GenAlClose
GenAlClose
GenAlarmOpen
Unit alarm
-
+/-
+/-
+
+
+
+
+/-
+/-
_
_
C
C
C
C
C
C
C
C
C
C
C
C
C
+
+
/
/
-
-
+
+
C
C
C
44
EH-105
ON/OFF INPUTS
EH-105
Press the
button to move the cursor to the On/Off input that you want to use.
Press
.
The
character blinks. Press the
and
button to select the digital input (21-27) or
measurement input (1-11) that you want the On/Off information in question
connected to. Exit from this mode by pressing
.
OK
-
+
ESC
TAKING INTO USE AND REMOVING FROM USE:
-
+ -
Cooling
HRU
Closing contact
Opening contact
Attention!
Only those On/Off
input functions illustrated here are
in effect that have been taken into
use by a connection point number.
MainPumpRun
In AC freq. converter
controlled AH units, Min and
Max indicate AH unit
outputs.
+/-
_
C
C
Instr.
p.23
Alarm situation:
Dampers open
Dampers close
AH start after
alarm is deactiv
No acknowledg.
After acknowl.
:
Is the drop from maximum to minimum output enabled
when the clock controls the AH unit to maximum output?