Select
Mainten.mode
Measurem. 7-11
Measurements 7-11 are 0…10V transmitter measurements. They can be
connected to pressure transmitters, CO2 content transmitters, humidity
transmitters, and air flow transmitters. These measurement channels can also be
used to receive On/Off information (see On/Off input selections p. 44)
Näytössä:
ADDITIONAL INFORMATION ABOUT TRANSMITTER MEASUREMENTS 7-11:
Measurements 7-11
Room temp
SF press
EF press
CO2 content
Rh/pot
SF flow
EF flow
SF filterPDE
EF filterPDE
HRU frostPDE
SF Fan PDE
EF Fan PDE
-
9
-
-
-
-
10
11
7
-
-
8
Transmitter area
0V =
ppm
10V =
ppm
0
2000
Transm./ Max Pa
0-10V
Pa
2-10V
Pa
4-20mA
Pa
500
500
500
Transm./ max m/s
0-10V
2-10V
4-20mA
10.0
10.0
10.0
Press the
button to select the transmitter output message.
Press
. The
character indicates what has been
selected. Press the and
button to set the amount of
pressure (Pa) at which the transmitter gives a maximum
message (10V or 20mA). Attention! Each pressure
transmitter measurement has its own settings.
Set which ppm content gives a 0V transmitter message and
which gives a 10V transmitter message. The range is 0
…2000 ppm.
Press the
button to select the transmitter output message.
Press
. The
character indicates what has been
selected. Press the and
button to set the volume of air flow
(m/s) at which the transmitter gives a maximum message (10V
or 20mA). The range is 0.0 …10.0 m/s.
OK
-
+
OK
-
+
Room temp
SF press
EF press
CO2 content
Rh/pot
SF flow
EF flow
SF filterPDE
EF filterPDE
HRU frostPDE
SF Fan PDE
EF Fan PDE
Room temperature
Supply air pressure (Measurement filtering: 30s time constant)
Exhaust air pressure (Measurement filtering: 30s time constant)
CO2 content of air
Room air humidity percentage or remote setting potentiom.(transmitter 0 …10V)
Supply air flow speed (used for flow detector function)
Exhaust air flow speed (used for flow detector function)
Pressure difference over supply air filter
Pressure difference over exhaust air filter
Pressure difference over the HRU. The controller switches on
defrost on the basis of measurement information, if needed.
Pressure difference over the supply fan or the air flow measurement ring
Pressure difference over the supply fan or the air flow measurement ring
-20...+100°C
0 ... 990Pa
0 ... 990Pa
0 ... 2000 ppm
0 .... 100%
0.0 ... 10.0 m/s
0.0 ... 10.0 m/s
0 ... 990Pa
0 ... 990Pa
0 ... 990Pa
0...5000Pa
0...5000Pa
Press the
button to move the cursor to the measurement that you want to take into
use. Press
. The cursor blinks at measurement channel information (strip
connector number). Press the
and
button to select which measurement channel
the measurement will be connected to. Measurement channels 7-11 can be selected.
Press
to exit. Press the
character to free a measurement channel that has
already been taken into use.
OK
-
+
ESC
-
43
EH-105
TRANS
MITTER MEASUREMENTS
TAKING INTO USE AND REMOVING FROM USE:
Free transmitter measurement channels (7-11) can also be
used for receiving On/Off information. (Taking On/Off
information into use, see p. 44)
Use of transmitter measurement channel for receiving
On/Off inputs:
Meas.7
Meas.8
Meas.9
Meas.10
Meas.1
1
7
8
9
10
11
On the display:
Explanation:
Range:
Attention! If an mA-transmitter is used, approx. a 500
parallel
resistance must be connected to the measurement input.
Transmitter area
0V
= 0 °C
10V = 50°C
Set a temperature (-20...0°C) that corresponds to a 0V
transmitter message and set a temperature(0...100°C) that
corresponds to a 10V transmitter message.
Taking transmitter measurements into use:
Instr.
p.23