Measurements 1-6
Outdoor temp
Supply temp
Exhaust temp
Room temp.
Supply tempB
Room temp B
Return water
Exh.aft.HRU
SupplyAft.HRU
RemoteSetPot
FreeMeasurem
1
2
3
-
-
-
4
-
-
-
-
Select
Mainten.mode
Measurem. 1-6
Measurements 1-6 are NTC measurements that are connected to Ouman
temperature sensors. These measurement channels can also be used to receive
On/Off information (see On/Off input selections p. 44). NTC measurements 2 - 6
have a range of -30 ... +100 °C. Outdoor temperature measurement is always
connected to measurement 1.
Outdoor temp
Supply temp
Supply temp B
ADDITIONAL INFORMATION ABOUT MEASUREMENTS 1 6:
Name change
FreeMeasurem
Give new label
Name change
FreeMeasurem
reeMeasurem
F
Labeling free measurements:
See page 6.
-50 ... + 50
-30 ... +100
-30 ... +100
1
2 - 6
2 - 6
EH-105
NTC- MEASUREMENTS
EH-105
NTC-
Press the
button to move the cursor to the measurement that you want to take into
use. Press
. The cursor blinks at measurement channel information (strip connector
number). Press the and
button to select which measurement channel the
measurement will be connected to. Measurement channels 2 - 6 can be selected.
Press
to exit. Press the character to free a measurement channel that has
already been taken into use.
OK
-
+
ESC
-
TAKING INTO USE AND REMOVING FROM USE:
Free NTC measurement channels (1-6) can also be used for receiving
On/Off information. (Taking On/Off information into use, see p. 44)
Use of NTC measurement channel for receiving On/Off inputs:
Meas.3
Meas.4
Meas.5
Meas.6
Meas.1
Meas.2
1
2
3
4
5
6
Room temp.
Exhaust temp.
Room temp. B
Return water
Exh.aft.HRU
SupplyAft.HRU
FreeMeasurem
RemoteSetPot
Room temperature
Exhaust air temperature
Room temperature sensor 2 temperature (for
computing the average)
Radiator return water temperature
Exhaust air (or glycol) temperature after the
HRU
Supply air temperature after the HRU
Free temperature measurement, which can be
labeled using the text editor
Remote setting potentiometre:
-Supply controlled and room controlled AH units
-30 ... +100
-30 ... +100
-30 ... +100
-30 ... +100
-30 ... +100
-30 ... +100
-30 ... +100
-5 …+4
1 - 6
1 - 6
2 - 6
2 - 6
2 - 6
2 - 6
2 - 6
2 - 6
B
42
On the display:
Explanation:
Range:
Measurement channel:
The
character indicates that the control in question is not in use.
-
Outdoor temperature
Supply air temperature
Supply air temperature before the cooling cell
(taking into account the process delay caused by the cooling cell during the heating period).
The controller changes the ”Supply tempB” sensor to be a controlling sensor when the
”Supply temp” deviates from the ”Supply temp B” by over 6 °C and the outdoor temperature is
below the cooling ”Outd.Inhibit”set value. Control switches back to the ”Supply temp” sensor
when the amount of deviation has been less than 5.5°C for 6 minutes.
Instr.