EH-105
The supply air information states which factors form the supply air temperature
determined by the controller at the time of inspection. With room/exhaust
controlled control, the controller calculates the supply air temperature setting
according to the room temperature. With supply controlled control the supply air
temperature is kept at the supply air temperature set value. The supply air
information changes according to different AH unit running situations as follows:
Supp.air.info °C
Room temp. 14.5
Room set.
18.5
RemoteSetPot-1.3
Room comp.
4.0
MaxDifHeat
0
MaxDifCool
0
Max limit
-1.0
Min limit
0.0
Start Incr. 0.0
Interaction21.5
FeezeAntic.
0%
Supp.air info °C
Room temp. 25.0
Room inst. 21.5
Cool.start 23.0
Cool. Need
2.0
P-roomCtrl
25%
I-roomCtrl
8%
Min limit
-13%
Cooling
-> 20%
Room comp. -6.5
I-roomCtrl -2.0
Min limit
1.0
Interaction16.0
During cooling:
Select
Measurements
AHU oper.contr.
Settings
Supply air info
AHU output info
KEYWORD:
Supply air info
Room set.
ExhaustTset
.
Room set.N
SupplyTset
Temp 2 set
Hint !
Hint !
The supply air
info helps you see which
factors are currently effecting
the supply air temperature.
AHU 1/1 Autom.
Room temp.21.2
SupplyTemp20.4
Selection
°C
°C
During heating:
During idle time:
Supp.air info °C
Returv.inst. 25
Retur.temp.
25
Room M set.16.0
Room temp. 18.5
Radiator return water temperature setting
Current radiator return water temperature
Room temperature night setting
Current room temperature
SUPPLY AIR INFO:
Room temp.22.8/
Room set.22.0/
Room comp.-2.7/
I-roomCtrl-3%/
MaxDifHeat 0.0/
MinDifCool 0.0/
Max limit0.0/
… Continuing...
11
Stepped
control
Continu-
ous
control
Room temp.
ExhaustTemp
SUPPLY AIR INFORMATION
Current supply temperature
Current room temperature or
Current exhaust air temperature.
Room temperature setting or
Exhaust air temperature setting or
Room temperature setting during night heating or
Supply temperature setting or
Temperature setting when the temperature control switch is
turned off. This is another setting for the room, exhaust, or
supply air temperature.
Room comp.
ExhausComp
Supply temp
MaxDiffHeat:
Effect of a room temperature deviation on the supply air temp.
Effect of an exhaust air temp. deviation on the supply air temp.
Supply air temperature drop due to the maximum limit
Increasing effect of the start-up phase on the supply air temperature (effects about 5
min. from start-up)
Supply air temperature increase due to the minimum limit
Current room temperature
Cooling need: Shows how much to drop the room temperature
Room temperature setting
Start-up temperature for cooling. The temperature must be higher than the room
setting by the amount of the heating/cooling hysteresis before cooling starts up
(=room s HeatCoolHyst)
Effect of P-room control on the cooling output in stepped control
Effect of I-room control on the cooling output in stepped control
The reducing effect of the supply air minimum limit on the cooling output in stepped
control
Effect of room compensation on the supply air temperature in continuous control
Current controller control of cooling (%) in stepped cooling
Current supply air temperature determined by the controller in continuous control
cooling
Effect of I-room control on the supply air temperature in continuous control
The increasing effect of the supply air minimum limit on the supply air temperature
The maximum limit for the difference between room and supply air
temperatures during heating
The maximum limit for the difference between room and supply air
temperatures during cooling
MaxDiffCool:
Current supply air temperature determined by the controller (°C)
Radiator return water anticipate freeze protection function as an additional control to
heating actuator control. (0…100%)
SUPPLY AIR INFO:
… Continuing...
Min limit1.0/
StartIncr. 0.0/
Interaction16.2/
FreezeAntic.=0%/