EH-105
OPERATING INSTRUCTIONS:
Ajan asetus
Supply air maximum limit and outdoor
temp. at which the max limit is reached.
Room temp.
ExhaustTemp
Temp. 2
SuppTempMax
SuppTempMin
Supply temp
Temp. 2
AHU 1/1 Autom.
Room temp.21.2
SupplyTemp20.4
Selection
°C
°C
AHUoutput/CO2ppm
Minimum /
Maximum/
CO2PostRun
min
600
1000
15
Damper
/CO2 ppm
Minimum /
Maximum /
600
1000
+22
17
-15
23
°C ->
°C
°C ->
°C
MoTuWeThFr_ _
OutdoorT->supp.T
08:00 ON
16:00 OFF
MoTuWeThFr_ _
The controller can control the AH unit
output and damper position according to
the CO content.
2
Ouman EH-105 has two different types of settings, user level and maintenance
level settings. The user can change the user level settings shown here if
necessary. Only a maintenance man authorised by Ouman can change the
maintenance level settings.
The settings that appear on the display vary depending on what settings and
measurements are connected to the controller.
Select
Measurements
AHU oper.contr.
Settings
Supply air info
A 5°C additional drop is activated
AHU output/CO2ppm
Start up
CO2PostRun
min
600
15
9
Room or exhaust controlled AH units:
Supply controlled AH units:
Outdoor temperature controlled AH units:
Supply air temperature setting.
Supply air temperature setting when the external temperature.
change switch is turned off (see p. 45).
-20.0...90.0°C
-20.0...90.0°C
-20.0...90.0°C
-20.0...90.0°C
-20.0...90.0°C
5 ... 95°C
-25 ... 90°C
21.5°C
22.5°C
21.5°C
21.5°C
22.5°C
32°C
17°C
Text on the
display:
SETTINGS
Browsing, making changes
or
Room temperature at which the night heating function is activated: the
AH unit which has been shut down starts up at full output and the
dampers go to the night heating position (see p. 34 N.HeatPosit).
When the room temperature rises by the amount of the hysteresis the
controller shuts down the AH unit and the dampers go to the idle time
position.
Attention! The exhaust controlled AH unit must have a room sensor
connected to it if the night heating function is going to be taken into
use.During night heating the room sensor controls the controller(p.25).
-15
+20
23
17
Supply air temp.
Outdoor temp.
5.0...45.0°C
-30...+30°C
Supply air temperature setting range
Outdoor temperature setting range
+22
17
-15
23
°C ->
°C
°C ->
°C
Outd.T->supp.T
Supply air minimum limit and outdoor
temp. at which the min. limit is reached.
Factory
settings:
Setting
range:
Explanation:
Settings °C
Supply temp
Outd.T/supp.T ->
Room temp.
Temp.2
SuppMinCool
Room temp N
Room temp N-5->
OutputChange
Damper min
%
DampMinCool
%
Damper max
%
MaintInter
h
AHUoutput/CO2->
Damper/CO2->
21.5
21.5
23.5
13
16.0
-15
30
30
100
6000
Browsing and making changes to settings:
-
+
OK
Press the
button to move the cursor to the setting you want to inspect or
change. Press the or
button to change the setting. Press
to confirm the
setting.
Room temperature setting.
Exhaust air temperature setting (exhaust controlled AH unit).
Room temperature (exhaust air) setting when the external
temperature change switch is turned off.
Supply air maximum temperature setting.
Supply air minimum temperature during the heating phase.
During summer the ”SupplyMinCool” setting is used, see p. 10.
A 5°C additional drop is inactivated
Constant pressure and constant speed AH
units
(pages 28, 31)
An additional drop of the night temperature setting occurs
(constant 5°C) at a selected time.
-20.0...90.0°C
16.0°C
Room temp N
Room temp N-5