APPENDIX C - VCB-X BACnet
®
VCB-X Controller Field Technical Guide
96
VCB-X BACnet
®
Parameters
BACnet
®
Properties for the VCB-X Controller
Parameter
Object
Description
Limits
Application
Software
Version
AI: 1
Current version of the
software in the unit.
Control Mode
AI:2
Con
fi
gured unit application.
See Control
Mode Bits on
page 104.
Control Status
AI: 3
Current Occupied/
Unoccupied Status.
See Control
Status Bits on
page 104.
HVAC Mode
AI: 4
Current operational status.
See HVAC
Mode Bits on
page 104.
Control
Temperature
AI: 5
Current value of the Control
Temperature Sensor.
Space
Temperature
AI:6
Current value of the Space
Temperature Sensor.
Supply Air
Temperature
AI:7
Current value of the
Supply Air
Temperature sensor.
Coil
Temperature
AI: 8
Current Coil
Temperature value.
Discharge
Temperature
AI:9
Current value of the
Discharge Air
Temperature Sensor.
Outdoor Air
Temperature
AI: 10
Current value of the
Outdoor
Temperature Sensor.
Return Air
Temperature
AI: 11
Current value of the Return
Temperature Sensor.
Leaving Water
Temperature
AI:12
Current value of the
Leaving Water
Temperature Sensor.
Outdoor Air
Wetbulb
Temperature
AI:13
Current calculated Outdoor
Wetbulb Temperature.
Outdoor Air
Dewpoint
Temperature
AI:14
Current Calculated Outdoor
Air Dewpoint Temperature.
Indoor Air
Humidity
AI: 15
Current value of the Indoor
Humidity Sensor.
Outdoor Air
Humidity
AI:16
Current value of the
Outdoor Humidity Sensor.
Duct Static
Pressure
AI:17
Current Duct Static
Pressure.
Building
Pressure
AI:18
Current value of the
Building Pressure Sensor.
Suction
Pressure
AI: 19
Current Suction Pressure
Value.
Head
Pressure 1
AI:20
Current Value of the Head
Pressure 1 Reading.
CO
2
AI:21
Current Indoor
CO
2
Level.
BACnet
®
Properties for the VCB-X Controller
Parameter
Object
Description
Limits
Outdoor
Air
fl
ow
AI: 22
Current Outdoor Air
fl
ow
Measurement.
Exhaust
Air
fl
ow
AI:23
Current Exhaust
Air
fl
ow Measurement
Supply Air
fl
ow
AI:24
Current Supply Air
fl
ow
Measurement.
Return Air
fl
ow
AI:25
Current Return Air
fl
ow
Measurement.
Cooling
Setpoint
AI:26
Occupied Cooling Mode
Enable Setpoint Mirror.
Heating
Setpoint
AI: 27
Occupied Heating Mode
Enable Setpoint Mirror.
Supply Air
Setpoint
AI: 28
Current SAT Cooling or
Heating Setpoint if there is
no reset source; Current
calculated SAT setpoint
with Reset Source.
Coil
Temperature
Setpoint
AI:29
This is the current
calculated Coil Suction
Temperature target during
Dehumidi
fi
cation Mode.
Head Pressure
Setpoint
AI:30
Current Head Pressure
Setpoint.
Indoor
Humidity
Setpoint
AI:31
This re
fl
ects the value set as
the Low Indoor Humidity
Reset Limit, which initiates
Dehumidi
fi
cation on indoor
controlled (non MUA)
units.
Economizer
Position
AI: 32
Current position of the
Economizer Damper.
Fan VFD
Signal
AI:33
Current Supply Fan VFD
Signal.
Modulating
Heating
Position
AI: 34
Current percentage of the
Modulating Heating signal
(Hot Water or SCR heat).
Modulating
Cooling
Position
AI: 35
Current percentage of the
Modulating Cooling Signal
(Chilled Water or Digital
Compressor).
Building
Pressure
Exhaust
Control Signal
AI: 36
Current Relief VFD Fan/
Damper Signal.
Reheat Valve
Position
AI:37
Current position of
MHGRV Modulating Hot
Gas Reheat Valve.
Modulating
Gas Valve
Position
AI:38
Current position of
MODGAS Modulating Gas
Valve Control.