VCB-X Controller Field Technical Guide
INSTALLATION & WIRING
25
GND
TMP
OE210, OE211, OE212, OE213
Space Temperature Sensor
OVR
R
E
L
O
C
R
E
M
R
O
A
W
AUX
Wire Required For
Sensors With Slide
Adjust Option Only
AI1
AI5
GND
VCB-X Controller
Space Temperature Sensor
The OE210, OE211, OE212, OE213 Space Temperature Sensor
is typically used for constant volume HVAC unit applications
controlling one zone. The Space Temperature Sensor is a 10K Type
III thermistor sensor and should be mounted approximately 5 feet
above the
fl
oor in the space that is to be controlled.
Figure 11: OE210, OE211, OE212, OE213 – Space Temperature Sensor Wiring and Slide Adjust
Space Temperature Sensor Wiring
The Space Temperature Sensor is available as a sensor only, sensor
with override button, sensor with slide adjust, and sensor with slide
adjust and override con
fi
gurations.
See
Figure 11
below for complete Space Temperature Sensor wiring
details.