User’s Manual
Section 5
Linear Output
8.
Use the LEFT and RIGHT keys to display
[FOCUS] on the main display.
Selecting current (mA) or voltage (V) output
9.
Press the UP or DOWN key.
The sub-display flashes.
10.
Display [mA].
Always select the same output as the current/voltage switch selection on the bottom of the Amplifier
Unit.
Setting the first point (A)
11.
Press the ENT key.
The display changes to the display for setting the first
point (A).
The output current value is displayed on the main
display.
The corresponding measured value is displayed on the
sub-display and the leftmost digit flashes.
12.
Set the output current value and the
corresponding measured value for the first point.
Set a measured value within the measuring range. If
scaling or calculation has been set, set a value that
reflects those settings.
The flashing digit, i.e., the digit to which a value can be set, changes as shown in the diagram
.
Moves from one digit to
another.
Changes the numeric value.
Digit shift on sub-display
Shifts one digit
at a time.
Switching from the sub-display to the main
display and vice versa (from the leftmost/
rightmost digit of the sub-display)