68
Online Errors and Warnings
Section 6-1
6-1
Online Errors and Warnings
Error messages: Messages indicating fatal errors
Warning messages: Dialog boxes are displayed for determining
processing. Follow the instructions given in the dialog boxes.
Note
This message is displayed when an attempt is made to go online
with only the CPU Unit specified in the property settings in the
Support Software, without having the Expansion I/O Unit
connected. Select "Y" to connect, and transfer the program.
This is supported for version 4.0 or higher.
Message
Probable cause
Countermeasure
Communications Error
has occurred.
No response to a
command from the ZEN
Support Software.
Communications timed out.
Check that the Computer Connecting
Cable is connected properly to the ZEN
and the computer serial port.
Check that the communications settings
match the connection configuration of the
ZEN.
Failed to connect to
ZEN. The connected
ZEN type ( ) does not
match the project’s
ZEN type ( ). Cannot
continue.
Online connection
attempted while the ZEN
system configuration and
the ZEN model in the ZEN
Support Software property
settings are not the same.
Change the ZEN model in the property
settings and the Expansion I/O Unit
settings to match the system configuration
of the ZEN to be connected online.
When only the Expansion I/O Unit
configuration is different, the following
warning message (bottom line) will be
displayed.
Operation failed since
ZEN is in RUN mode.
STOP ZEN running.
Command executed from
the ZEN Support Software
while the ZEN is in RUN
mode.
Change the ZEN to STOP mode and re-
execute the command.
Operation failed since
ZEN is protected.
Release the protection.
Command executed from
the ZEN Support Software
while the ZEN is protected.
Remove the protection from the ZEN and
re-execute the command.
Operation failed since
LCD is operating.
Restore the main
screen of LCD.
Command executed from
the ZEN Support Software
while LCD operations being
performed on the ZEN.
Return the LCD operations to the Main
Screen and re-execute the command.
Error rung found in the
program. Program
transfer is cancelled.
There is an error in the
program.
Refer to the probable causes and
countermeasures for Program Check error
messages.
Messages
ZEN is in RUN mode; execution not possible. Change to STOP mode? Y/N
Return to RUN mode? Y/N
A circuit in the program generated a warning. Continue program transfer?
ZEN model in properties settings (****) does not match model being connected (****). Go online?
Y/N (See note.)