2-1
Section
Amplifiers
14
Allocated I/O Words
Point
Input (IN)
Word X
Word (X+1)
0
ID0
ADDR0
1
ID1
ADDR1
2
ID2
ADDR2
3
ID3
ADDR3
4
ID4
ADDR4
5
ID5
ADDR5
6
ID6
ADDR6
7
ID7
ADDR7
8
ID8
WT_MODE1
9
ID9
WT_MODE2
10
ID10
WT_BYTE
11
ID11
WT_AREA
12
ID12
Reserved. (See note 1.)
13
ID13
Reserved. (See note 1.)
14
ID14
READ/WRITE
15
ID15
INHIBIT/TRG
Point
Output (OUT)
Word Y
Word (Y+1)
0
OD0
EXT OD16
1
OD1
EXT OD17
2
OD2
EXT OD18
3
OD3
EXT OD19
4
OD4
EXT OD20
5
OD5
EXT OD21
6
OD6
EXT OD22
7
OD7
EXT OD23
8
OD8
Not used.
9
OD9
Not used.
10
OD10
Not used.
11
OD11
Not used.
12
OD12
Not used.
13
OD13
ERROR
14
OD14
NORMAL
15
OD15
HS
Note
1. Reserved inputs must be used as 0.
2. Refer to
Appendix B I/O Allocations for examples of I/O allocations. For de-
tails, refer to the
CompoBus/D (DeviceNet) Operation Manual (W267).