4-2
Section
Installing Sensors
48
In addition to surface mounting, it is also possible to flush-mount the V600-H67
Sensor within a metal casing to protect it from being struck by other objects. To
prevent malfunctioning, allow at least 50 mm between the sides of the Sensor
and the metal casing, and do not mount the Sensor below the metal surface. If it
is less than 50 mm, the transmission distance will be greatly reduced.
50 min.
50 min.
50 min.
50 min.
11 radius
min.
50 min.
30 max.
Metal casing
Metal casing
(Unit: mm)
Note
1. Do not bend the Sensor’s cable into a curve tighter than 11 mm in radius.
2. The read/write transmission range will be reduced significantly if the Sensor
is installed closer than 50 mm to metal surfaces.
4-2-3 Mutual Interference Between Sensors
When using multiple Sensors, be sure to install them at the distances shown be-
low in order to prevent malfunctions due to mutual interference.
When facing each other or facing the same direction, V600-HS51 Sensors
should be installed at least 80 mm apart.
80 mm min.
80 mm min.
V600-HS51
V600-HS51
V600-
HS51
V600-
HS51
When facing each other or facing the same direction, V600-HS61 Sensors
should be installed at least 80 mm apart.
80 mm min.
80 mm min.
V600-HS61
V600-HS61
V600-
HS61
V600-
HS61
80 mm min.
V600-HS61
V600-HS61
V600-HS67
V600-HS51
V600-HS61