6-3
Section
Transistor Output Units
78
Note
V terminals and G terminals are internally connected. When the I/O power is
being supplied, the power can be supplied to the output devices from the V
terminals and G terminals. Current supplied in this way, however, must be less
than 4 A.
Dimensions
(Unit: mm)
Approx. 89
Note
The vertical center of the Unit is 4.9 mm lower than the center of the DIN track.
The Unit therefore extends downward 41.4 mm (including the mounting hook)
from the DIN track center.
6-3-3 GT1-OD16MX Transistor Output Unit with Connector (NPN)
Output Specifications
Item
Specifications
Number of outputs
16 points
Current per common
2 A max.
Components
Digital Output Connectors
(made by MOLEX)
Connect to output devices,
such as relays and solenoids.
Terminal Block
DIN Track Mounting Hook
I/O Unit Interface
Communications Connector 1
(on the Communication Unit side)
TS Indicator
(Refer to page 162.)
Output Indicators
Display the status of the outputs.
Lit when an output is ON.
I/O Unit Interface
Communications Connector 2
(on the terminator Side)