7-2
Section
Analog Output Units
130
Attach MOLEX connectors to the analog output connectors, and connect the
outputs as shown in the following diagram.
Applicable Connectors
Manufac-
turer
Connector
Model number
Remarks
MOLEX
Pressure-
welded
Housing
521-09-0390
For AWG#24
Crimp
Housing
50-57-9403
p
Reeled contacts 16-02-0069
For AWG#24 to 30
16-02-0086
For AWG#22 to 24
Loose contacts
16-02-0096
For AWG#24 to 30
16-02-0102
For AWG#22 to 24
Crimping tool
570-36-5000
For AWG#22 to 26
p g
11-01-0209
For AWG#24 to 30
External
device
Source
24 VDC
+
--
The Analog Output Unit converts the digital output data to analog values. The
analog values depend on the output signal ranges, as shown in the following
diagrams.
1 to 5 V
The hexadecimal values 0000 to 1770 (0 to 6000) correspond to an analog
voltage range of 1 to 5 V. The entire output range is 0.8 to 5.2 V.
Converted data
Hexadecimal
(Decimal)
Voltage
5.2 V
5 V
1 V
0.8 V
0 V
FED4
(--300)
1770
(6000)
189C
(6300)
8000
0000 (0)
7FFF
Wiring
Output Ranges and
Converted Data