7-2
Section
Analog Output Units
123
Internal power supply
Internal power supply
Voltage output
Shield
External
output
Current output
Shield
External
output
The Analog Output Unit converts the digital output data to analog values. The
analog values depend on the output signal ranges, as shown in the following
diagrams.
1 to 5 V
The hexadecimal values 0000 to 1770 (0 to 6000) correspond to an analog
voltage range of 1 to 5 V. The entire output range is 0.8 to 5.2 V.
Converted data
Hexadecimal
(Decimal)
Voltage
5.2 V
5 V
1 V
0.8 V
0 V
FED4
(--300)
1770
(6000)
189C
(6300)
8000
0000 (0)
7FFF
Terminal Arrangement
Wiring
Output Ranges and
Converted Data