7-2
Section
Analog Output Units
131
0 to 5 V
The hexadecimal values 0000 to 1770 (0 to 6000) correspond to an analog
voltage range of 0 to 5 V. The entire output range is --0.25 to 5.25 V.
Converted
data
Hexadecimal
(Decimal)
Voltage
5.25 V
5 V
0 V
8000 FED4 (--300)
--0.25 V
1770
(6000)
189C
(6300)
0000 (0)
7FFF
0 to 10 V
The hexadecimal values 0000 to 1770 (0 to 6000) correspond to an analog
voltage range of 0 to 10 V. The entire output range is --0.5 to 10.5 V.
Converted
data
Hexadecimal
(Decimal)
Voltage
10.5 V
10 V
0 V
8000 FED4 (--300)
--0.5 V
1770
(6000)
189C
(6300)
0000 (0)
7FFF
--10 to 10 V
The hexadecimal values F448 to 0BB8 (--3000 to 3000) correspond to an analog
voltage range of --10 to 10 V. The entire output range is --11 to 11 V. Specify a
negative voltage as a two’s complement (16 bits).
Converted data
Hexadecimal
(Decimal)
Voltage
11 V
10 V
F31C
(--3300)
F448
(--3000) 0000 (0)
0 V
--10 V
--11 V
8000
7FFF
0BB8
(3000)
0CE4
(3300)