CLTI- & CLXI-2DIM2

 

Terminal Block & Module Locations (Single-wide Enclosure) 

Functional Summary 

MODULE

TERMINAL

BLOCK

GROUNDING

TERMINAL

BLOCK

(INSTALL INTO

LOWEST

AVAILABLE

SPACES)

 

The Crestron

 2-Feed, 2-Dimmer Terminal Block and 

Module (CLTI-2DIM2 and CLXI-2DIM2, respectively), 
are considered a single entity and must be used together. 
They ship separately to permit termination of the field 
wiring to the CLTI-2DIM2 prior to installation of the 
CLXI-2DIM2, as described in this guide. They can be 
mounted in any Crestron Automation Enclosure (CAEN-
Series Enclosures). The terminal block is designed to 
terminate two circuit feeds (HOT and NEUTRAL) and 
distribute the controlled circuits (LOAD) to the fixtures. 
The module connects to the terminal block and performs 
dimming control of two incandescent, magnetic low 
voltage, neon, cold cathode, or dimmable 2-wire 
fluorescent lighting loads. The maximum load is 10 amps 
for each controlled circuit (20 amps total per module). 
The unit requires 230VAC 50 Hz, 1 phase input voltage. 
An oversize heat sink dissipates heat efficiently. There are 
LEDs on the module to indicate communication to a 
Cresnet

 network, input power to the module, and output 

power to the load. 

NOTE:  

The two input lines must be the same phase 

or split phase. 

Terminal Block & Module Locations (Double-wide Enclosure) 

NOTE:  

When connecting to an Arc Fault Breaker, 

the load should not exceed 1000 watts.  

GROUNDING TERMINAL BLOCKS

TERMINAL BLOCK

(LEFT)

TERMINAL BLOCK

(RIGHT)

MODULE

(INSTALL INTO

LOWEST

AVAILABLE

SPACES)

 

Installation 

Terminal block and module must be mounted into a 
Crestron Automation Enclosure by a licensed electrician, 
in accordance with all national and local codes.  

CAUTION:  

This equipment is for indoor use only 

and needs to be air-cooled. Mount in a well-
ventilated area. The ambient temperature must be 
0

°

C to 40

°

C (32

°

F to 104

°

F). The relative humidity 

must be 0% to 90% (non-condensing).  

Terminal blocks are installed along the left side of single-
wide enclosures and along the outside edges (left and 
right sides) of double-wide enclosures. Modules are 
installed along the right side of single-wide enclosures 
and side-by-side in the center of double-wide enclosures. 
When installing modules and terminal blocks in a double-
wide enclosure, be sure to invert units on the right side so 
that they can be properly wired. Refer to the illustrations 
shown below when considering the location of terminal 
blocks and modules within an enclosure.  

NOTE:  

Modules and terminal blocks must be 

installed into the lowest available spaces and 
continue toward the top of the enclosure. 

Crestron Electronics, Inc.

 

Installation Guide – DOC. 6410

 

15 Volvo Drive   Rockleigh, NJ 07647

 

(2013810)

 

Tel: 888.CRESTRON

 

11.05

 

Fax: 201.767.7576

  

Specifications subject to 

 

www.crestron.com

 

change without notice.

 

Summary of Contents for CLTI-2DIM2

Page 1: ...ns Double wide Enclosure NOTE When connecting to an Arc Fault Breaker the load should not exceed 1000 watts GROUNDING TERMINAL BLOCKS TERMINAL BLOCK LEFT TERMINAL BLOCK RIGHT MODULE INSTALL INTO LOWEST AVAILABLE SPACES Installation Terminal block and module must be mounted into a Crestron Automation Enclosure by a licensed electrician in accordance with all national and local codes CAUTION This eq...

Page 2: ...ll circuits receive power Do not remove these bypass jumpers until all feed and load wiring has been completed the circuit has been tested for electrical faults and the module has been installed Refer to Module Installation on next page Jumpers are also installed on the blue sections of the terminal block and tie all neutrals together These jumpers should never be removed Wiring Diagram of the Ter...

Page 3: ...color as the terminal to which it should be connected Wires are pre stripped to 12 mm Tighten to 1 Nm Do not over tighten 3 If the module is being installed above another module within the enclosure attach the supplied module interconnect cable between the two modules The illustration below depicts the area within a double wide enclosure where the corners of four modules meet NOTE One wire on the ...

Page 4: ...following repair of items under warranty shall be paid by CRESTRON shipping by standard ground carrier In the event repairs are found to be non warranty return freight costs shall be paid by the purchaser CRESTRON Limited Warranty CRESTRON ELECTRONICS Inc warrants its products to be free from manufacturing defects in materials and workmanship under normal use for a period of three 3 years from the...