2-16
List of Settings
Section 2
Lis
t of
Se
ttings
Linear Output Level
Note
The values beginning with H' in the
Monitor/Setting range
column are used when setting or monitor-
ing data via communications.
Communications Setting Level
Note
The values beginning with H' in the
Monitor/Setting range
column are used when setting or monitor-
ing data via communications.
Advanced Function Setting Level
Note
(1) If the event connector is provided as a standard feature or an event connector is added, use EV
for the “bank selection” set.
(2) The values beginning with H' in the
Monitor/Setting range
column are used when setting or moni-
toring data via communications.
Variable
type
Address
Parameter
name
Charac-
ter
Monitor/Setting range
Character
Default
setting
Decimal point
Unit
C9
0000
Linear current
type
lset.
c
H’00000000: 0-20 mA (0), H’00000001: 4-20 mA (1)
0-20
,
4-20
4-20
---
---
0001
Linear voltage
type
lset.
v
H’00000000: 0-5 V (0), H’00000001: 1-5 V (1),
H’00000002: 0-10 V (2)
0-5
,
1-5
,
0-10
1-5
---
---
0002
Linear output
upper limit
lset.
h
H’FFFFB1E1 to H’0001869F:
−
19999 to 99999
(Time limit is OFF. Lower limit of P is 0.)
H’00000000 to H’0001869F: 0 to 99999
(Time unit is min.)
H’00000000 to H’000176D7: 0.00.00 to 9.59.59
(Time unit is hr:min:s.)
H’00000000 to H’0001850F: 00.00.0 to 99.59.9
(Time unit is min:s:ms.)
:9999
to
99999
0.
00.
00
to
99999
0.
00.
00
to
9.
59.
59
0.
00.
00
to
99.
59.
9
99999
According to the
decimal position
setting. The time
unit, however, is
indicated as
*.**.** for
hr:min:s and as
**.**.* for
min:s:ms.
---
0003
Linear output
lower limit
lset.
l
Same as above
Same as above
R:
:9999
P:
0
Same as above
---
Variable
type
Address
Parameter
name
Charac-
ter
Monitor/Setting range
Character
Default
setting
Decimal point
Unit
CA
0000
Communications
unit number
u-no
H’00000000 to H’00000063: (0 to 99)
0
to
99
1
---
---
0001
Baud rate
bps
H’00000000: 9.6 (0), H’00000001: 19.2 (1),
H’00000002: 38.4 (2)
9.
6
,
19.
2
.
38.
4
9.
6
---
kbps
0002
Communications
data length
len
H’00000000: 7 (0), H’00000001: 8 (1)
7
,
8
7
---
bit
0003
Communications
stop bits
sbit
H’00000000: 1 (0), H’00000001: 2 (1)
1
,
2
2
---
bit
0004
Communications
parity
prty
H’00000000: None (0), H’00000001: Even (1),
H’00000002: Odd (2)
none
,
even
,
odd
even
---
---
0005
Send wait time
sdwt
H’00000000 to H’00000063: (0 to 99)
0
to
99
20
---
ms
Variable
type
Address
Parameter
name
Charac-
ter
Monitor/Setting range
Character
Default
setting
Decimal point
Unit
CB
0000
PASS output
change
pass
H’00000000: LL (0), H’00000001: L (1),
H’00000002: PASS (2), H’00000003: H (3),
H’00000004: HH (4)
ll
,
l
,
pass
,
h
,
hh
pass
---
---
0001
Hysteresis
hys
H’00000000 to H’0000270F: 0 to 9999 (Time limit is
OFF. Lower limit of P is 0.)
H’00000000 to H’00001747: 0.00.00 to 0.59.59
(Time unit is hr:min:s.)
H’00000000 to H’0000257F: 00.00.0 to 09.59.9
(Time unit is min:s:ms.)
0
to
9999
0.
00.
00
to
0.
59.
59
00.
00.
0
to
09.
59.
9
1
According to the
decimal position
setting. The time
unit, however, is
indicated as
*.**.** for
hr:min:s and as
**.**.* for
min:s:ms.
---
0002
Output OFF delay
off-d
H’00000000 to H’000007CF: (0 to 1999)
0
to
1999
0
---
R:
100 ms
P: ms
0003
Shot output
shot
H’00000000 to H’000007CF: (0 to 1999)
0
to
1999
0
---
R:
100 ms
P: ms
0004
Output logic
out-n
H’00000000: Close in alarm (0),
H’00000001: Open in alarm (1)
n-o
,
n-c
n-o
---
---
0005
Output refresh
stop
o-stp
H’00000000: OFF (0), H’00000001: OUT (1),
H’00000002: ALL (2)
off
,
out
,
all
off
---
---
0009
Bank selection
bnk-c
H’00000000: OFF (0), H’00000001: KEY (1),
H’00000002: EV (2)
off
,
key
,
ev
off
(See
note 1.)
---
---
000A
Startup
compensation
timer
s-tmr
H’00000000 to H’0000270F: (0.0 to 99.9)
0.
0
to
99.
9
0.
0
1
s
000C
Standby
sequence
stdby
H’00000000: OFF (0), H’00000001: ON (1)
off
,
on
off
---
---
Summary of Contents for K3HB
Page 2: ...K3HB Digital Indicators Communications User s Manual Revised March 2005...
Page 3: ...iv...
Page 15: ...xvi...
Page 19: ...xx...
Page 21: ...Part 1 CompoWay F...
Page 69: ...Part 2 DeviceNet...
Page 95: ...6 10 Ladder Programming Examples Section 4 3 Remote I O Com munications...
Page 111: ...8 8 Message Communications Performance Section 6 2 Communications Performance...
Page 127: ...Part 3 BCD Output...
Page 147: ......