7-7
Explicit Messages Specific to DeviceNet-compatible Digital Indicators
Section 5-3
Expl
ic
it M
essage
C
o
m
m
uni
cat
ions
5-3-1
Reading General Status
5-3-2
Writing Maintenance Mode Data
5-3-3
Setting and Monitoring the Digital Indicator Words
Explicit
message
Read/
write
Function
Command
Response
Service
code
Class
ID
Instance
ID
Attribute
ID
Data
size
General
Status
Read
Read
Reads the DeviceNet-com-
patible Digital Indicator’s
general status bits (8 bits).
(Refer to page 6-5).
0E hex
95 hex 01 hex
65 hex
---
1 byte
Explicit
message
Read/
write
Function
Command
Response
Service
code
Class
ID
Instance
ID
Attribute
ID
Data
size
Mainte-
nance
Counter
Save
Save
Records the maintenance
counter (PV of Unit con-
duction time for all Digital
Indicators) in memory.
16 hex
95 hex
01 hex
75 hex
---
---
Explicit
message
Read/
write
Function
Command
Response
Service
code
Class
ID
Instance
ID
Attribute
ID
Data size
Set Value
for Unit
Conduction
Time
Read
Reads the set value
(monitor value) for the
Unit conduction time
(unit: 0.1 h (6 min)).
0E hex
7A hex 01 hex
68 hex
4 bytes
00000000 to
FFFFFFFF
hex (0 to
4294967295)
Write
Writes the set value
(monitor value) for the
Unit conduction time
(unit:0.1 h (6 min)).
10 hex
7A hex 01 hex
68 hex
4 bytes
00000000
to
FFFFFFFF
hex (0 to
429496729
5)
Unit Con-
duction
Time Read
Read
Reads the PV for the
Unit conduction time
(unit: 0.1 h (6 min)).
0E hex
7A hex 01 hex
66 hex
4 bytes
00000000 to
FFFFFFFF
hex (0 to
4294967295)
Monitor
Status of
Unit Con-
duction
Time Read
Read
Reads the monitor sta-
tus for the Unit conduc-
tion time.
0E hex
7A hex 01 hex
67 hex
1 byte
00 hex: Within
range
01 hex: Out of
range (moni-
tor value
exceeded)
Summary of Contents for K3HB
Page 2: ...K3HB Digital Indicators Communications User s Manual Revised March 2005...
Page 3: ...iv...
Page 15: ...xvi...
Page 19: ...xx...
Page 21: ...Part 1 CompoWay F...
Page 69: ...Part 2 DeviceNet...
Page 95: ...6 10 Ladder Programming Examples Section 4 3 Remote I O Com munications...
Page 111: ...8 8 Message Communications Performance Section 6 2 Communications Performance...
Page 127: ...Part 3 BCD Output...
Page 147: ......